Electrical data • Caracteristicas eléctricas
Charactéristiques electrique • Dados eléctricos
Max. power input
absorbida y fusible recomendado
Consommation maximale
Potência máx. absorvida
Supply voltage (see type plate)
Tensión de entrada (ver etiqueta identificativa)
Alimentation électrique (voir plaque sign.)
Tensão de rede (ver placa indicadora)
Recommanded cable jacket diameter
Diámetro exterior del cable recomendado
diamètre recommandé pour la gaine du câble
Diâmetro recomendado do invólucro de cabo
Cable cross-section and fuse protection
Sección de cable y fusible
Section des fils et fusibles
Secção do cabo e fusível recomendado
Contact loading
Carga del contacto
Pouvoir de coupure
Carga de contato
*) time lag / lento / temporisée / de ação média lenta
Maintenance • Mantenimiento • Entretien • Manutenção
x
x
x
x
x
12
230/110/24/...
P < 2,0 VA
Uac = ... ±10%
50 – 60 Hz
3 x 0,75 mm² / 5 x 0,25 mm²
x
x
x
x
Alarm
TEST
Valve
Power
24 Vdc
Vac
P < 2,0 W
U
= 24Vdc
0
-10/+25%
ø 5,8 - 8,5 mm
0,5 A *)
100 mA *) **)
<250Vac/<0,5A
>12Vdc/>50mA
english
Potential-free contact
The alarm signal can be relayed via a
potential-free contact. The changeo-
ver contact can be operated, e.g., in
the fail-safe mode.
When operating voltage is being app-
lied and the BEKOMAT device is
functioning correctly, the alarm relay
is energized. The contact element (0.7
- 0.8).
When there is no operating voltage or
in the case of a fault signal, the alarm
relay drops out. The contact element
is open (alarm).
Externeral test button (optional)
Here, the normal test button function
has been extended for additional use
outside the BEKOMAT unit. This
makes it possible to discharge any
condensate in the unit by remote
control, if required. When the external
contact closes, the valve will open.
**) min. internal resistance of
voltage source Ri> 12 Ohm
Maintenance recommendation:
• Housing and valve should be
cleaned once a year
• Replace wearing parts once a year.
Set of wearing parts ( x )
BEKOMAT 16 CO
Functional test of BEKOMAT device:
• Press test button approx. 2 sec.
• Valve opens for condensate discharge.
Checking of alarm signal:
• Shut off condensate inflow.
• Press test button for at least 1 min.
• Red LED flashes (after 1 minute).
• Alarm signal is being relayed.