Liste attribution (h)
Param PW Description
h01 ........ tec ... Fonction du relais 1 ............................................. --- = Désactivé, on= on permanent, alA = Alarme, Avertissement, .........alA ......... alA
h02 ........ tec ... Fonction du relais 2 (SSR) .................................Idem ................................................................................................................L1 ........... L1
h03 ........ tec ... Fonction du relais 3 (SSR) .................................Idem ................................................................................................................--- ......... ---
h04 ........ tec ... Fonction du relais 4 .............................................Idem. ...............................................................................................................--- ......... ---
h05 ........ tec ... Fonction du relais 5 (SSR) .................................Idem. ...............................................................................................................--- ......... ---
h06 ........ tec ... Fonction relais 1 du BMR (SSR) ..........................Idem ....................................................................................................................--- .......... ---
h07 .........tec ... Fonction relais 2 du BMR (SSR) ..........................Idem. ...................................................................................................................--- .......... ---
h08 .........tec ... Fonction relais 3 du BMR (SSR) ..........................Idem ....................................................................................................................--- .......... ---
h09 .........tec ... Fonction relais 4 du BMR (SSR) .........................Idem. ...............................................................................................................--- ......... ---
h20 .......oem .. Type de sonde ....................................................201 = TF201, 501 = TF501, 5o1, 5o2 = sondes spécifi ques ....................501 ......... 501
h21 .......oem .. Fonction sonde 1 ................................................--- = Déconnectée, d
h22 .......oem .. Fonction sonde 2 ................................................Idem. ...............................................................................................................--- ......... ---
h23 .......oem .. Fonction sonde 3 ................................................Idem ................................................................................................................--- ......... ---
h24 .......oem .. Fonction sonde 4 ................................................Idem ................................................................................................................--- ......... ---
h25 .......oem .. Fonction capteur de pression 1, 4/20mA ...........Idem ................................................................................................................Lco ......... Lco
h26 .......oem .. Fonction capteur de pression 2, 4/20mA ...........Idem ................................................................................................................--- ......... ---
h31 .......oem .. Fonction entrée opto-coupleur DI1 .....................--- = Déconnectée, .....................................................................................--- ......... ---
"X" = paramètres uniquement visualisables, ne pouvant
pas être modifi és.
Nota
"PW" = code requis selon le niveau d'utilisateur.
Le régulateur comporte 3 niveaux d'utilisateur :
- Code OEM (oem) : Mois + Heure + 20
- Code technicien (tec) : 88
- Code client (---) : Aucun code requis
h32 .......oem .. Fonction entrée opto-coupleur DI2 .....................Idem
h33 .......oem .. Fonction entrée opto-coupleur DI3 .....................Idem
h34 .......oem .. Fonction entrée opto-coupleur DI4 .....................Idem
h40 .......oem .. Sortie analogique délivrant .................................420 = signal 4-20mA , 010= signal 0-10V ....................................................010 ......... 010
h41 .......oem .. Sortie analogique utilisée comme ......................--- = 0V / 4 mA .............................................................................................--- ......... ---
h49 ........ tec ... Régul. compresseur avec système CRII ......... 0 = non, 1 = oui (1 comp.) .............................................................................................. 0 0
h50 ........ tec ... Moteur prioritaire ................................................ 0 = même priorité, 1 = Moteur 1, 2 = Moteur 2, 3 = Moteur 3, 4-8 = idem. ..0 ............. 0
h51 ........ tec ... Nombre d'étages BP moteur 1 .......................... 0...8 ..................................................................................................................1 ............. 1
h52 ........ tec ... Nombre d'étages BP moteur 2 .......................... 0...8 ..................................................................................................................0 ............. 0
h53 ........ tec ... Nombre d'étages BP moteur 3 .......................... 0...8 ..................................................................................................................0 ............. 0
h54 ........ tec ... Nombre d'étages BP moteur 4 .......................... 0...8 ..................................................................................................................0 ............. 0
h55 ........ tec ... Nombre d'étages BP moteur 5 .......................... 0...8 ..................................................................................................................0 ............. 0
h56 ........ tec ... Nombre d'étages BP moteur 6 .......................... 0...8 ..................................................................................................................0 ............. 0
h57 ........ tec ... Nombre d'étages BP moteur 7 .......................... 0...8 ..................................................................................................................0 ............. 0
h58 ........ tec ... Nombre d'étages BP moteur 8 .......................... 0...8 ..................................................................................................................0 ............. 0
h61 ........ tec ... Etage 1 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h62 ........ tec ... Etage 2 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h63 ........ tec ... Etage 3 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h64 ........ tec ... Etage 4 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h65 ........ tec ... Etage 5 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h66 ........ tec ... Etage 6 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h67 ........ tec ... Etage 7 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h68 ........ tec ... Etage 8 (BP) inversé .......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h71 ........ tec ... Nombre d'étages HP moteur 1 .......................... 0...8 ..................................................................................................................0 ............. 0
h72 ........ tec ... Nombre d'étages HP moteur 2 .......................... 0...8 ..................................................................................................................0 ............. 0
h73 ........ tec ... Nombre d'étages HP moteur 3 .......................... 0...8 ..................................................................................................................0 ............. 0
h74 ........ tec ... Nombre d'étages HP moteur4 ........................... 0...8 ..................................................................................................................0 ............. 0
h75 ........ tec ... Nombre d'étages HP moteur 5 .......................... 0...8 ..................................................................................................................0 ............. 0
h76 ........ tec ... Nombre d'étages HP moteur 6 .......................... 0...8 ..................................................................................................................0 ............. 0
h77 ........ tec ... Nombre d'étages HP moteur 7 .......................... 0...8 ..................................................................................................................0 ............. 0
h78 ........ tec ... Nombre d'étages HP moteur 8 .......................... 0...8 ..................................................................................................................0 ............. 0
h81 ........ tec ... Etage 1 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h82 ........ tec ... Etage 2 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h83 ........ tec ... Etage 3 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h84 ........ tec ... Etage 4 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h85 ........ tec ... Etage 5 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h86 ........ tec ... Etage 6 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h87 ........ tec ... Etage 7 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h88 ........ tec ... Etage 8 (HP) inversé ......................................... 0 = non, 1 = oui ...............................................................................................0 ............. 0
h90 ........oem .. Enregistrer la confi guration (avec code OEM) ...--- = quitter sans sauvegarder (avec la touche RET) .................................--- ......... ---
h91 ......... 70 .... Charger une confi guration (avec le code 70) .. --- = non ........................................................................................................--- ......... ---
h92 ......... tec ... Module d'extension BMR 3002 disponible ........ 0 = non, 1 = oui ...............................................................................................0 ............. 0
h93 ........ tec ... Seuil bas capteur de pression 1 ........................ -1,0...160,0 bar ..............................................................................................-1,0 bar ...-1,0 bar
h94 ........ tec ... Seuil haut capteur de pression 1 ....................... -1,0...160,0 bar ..............................................................................................+9,0 bar ..+9,0 bar
h95 ........ tec ... Seuil bas capteur de pression 2 ........................ -1,0...160,0 bar ..............................................................................................-1,0 bar ...-1,0 bar
h96 ........ tec ... Seuil haut capteur de pression 2 ....................... -1,0...160,0 bar ..............................................................................................+9,0 bar ..+9,0 bar
h99 ........ tec ... Type de fl uide frigorigène .................................. - - - = non utilisée - Régulation par sonde de température uniquement .......2 ............. 2
Notice technique Régulateur d'étages MSR eco 3140
Plage
SuA = Alarme surchauffe aspi.
L1 = étage 1 BP, l2 = étage 2 BP, L3 = étage 3 BP, L4 = étage 4 BP
L5 = étage 5 BP, l6 = étage 6 BP, L7 = étage 7 BP, L8 = étage 8 BP
K1 = étage 1 HP, K2 = étage 2 HP, K3 = étage 3 HP, K4 = étage 4 HP
K5 = étage 5 HP, K6 = étage 6 HP K7 = étage 7 HP, K8 = étage 8 HP
s = Sonde d'affi chage, Lco = Sonde régul. BP,
i
Hco = Sonde régul. HP, out = Temp. extérieure, Sut = Sonde conduite aspi. .--- ......... ---
L(1 = Délestage 1, L(2 = Délestage 2,
FbL = Retour forcé (si 0V), fbK = Retour forcé (si 230V),
dnL = Marche de nuit (si 0V), dnK = Marche de nuit (si 230V),
LFL = Défaut externe BP (si 0V),
LFK = Défaut externe BP (si 230V),
KFL = Défaut externe HP(si 0V),
KFK = Défaut externe HP (si 230V),
r1 = Signal de retour - Moteur 1 BP,
r2 = Signal de retour - Moteur 2 BP,
r3 = Signal de retour - Moteur 3 BP,
r4 = Signal de retour - Moteur 4 BP,
........................................................................................................--- ......... ---
........................................................................................................--- ......... ---
........................................................................................................--- ......... ---
100 = 100% (10V - 20 mA respectivement),
LP
= Sortie pour régulation PI (BP)
i
KP = Sortie pour régulation P (HP)
do = enregistrer (avec la touche RET)
cF1 = Confi guration 1, cF2 = Confi guration 2,
cFU = Confi guration utilisateur
1= NH3, 2= R134a, 3= R22, 4= R23,
5= R404a, 6= R507, 7= R402A, 8= R402B,
9= R407C, 10= R123, 11= R290, 12= CO2, 13= R502, 14= R723,
15= R410A, 16= R407F, 17= R448A, 18= R449A