Problem
High salt or magnesium con-
sumption
No or insufficient magnesium
consumption
Differential pressure at the device
is too high
Water pressure reduction / slowly
decreasing effectiveness
Too much water in the storage
tank
Magnesium build up in cabinet
Formation of brown sediment in
the storage tank
Time is flashing
Incorrect display „H——25"
Irregular removal of magnesium
in the cabinet, "magnesium accu-
mulation" on cabinet wall
Extremely high salt consumption Control orifice got stuck
*CS = Customer Service
www.honeywell.com
GB
Cause
Incorrect settings at the control valve Check the control valve settings
Blending has been set incorrectly
Too much water in the storage tank
Incorrect settings at the control valve Check the control valve settings
Blending has been set incorrectly
Brine tube is contaminated
Nozzles clogged
Construction of the device is too small Call Technical Customer Service
Blending has been closed too widely Check blending and mixing ratio (
Pipework of the drinking water supply
is calcified or blocked
Control valve is contaminated or de-
fective
Water meter is contaminated or defec-
tive
Increasing iron deposit in the resin
Brine tube is contaminated
Drain tube is blocked
Incorrect settings at the control valve Check the control valve settings
Brine valve is contaminated or defecti-
ve
May be caused by temperature fluctu-
ations in the cabinet
Normal excretions from consumables Remove when cleaning
Device suffered a power failure
Operating program has been deleted Call Technical Customer Service
Magnesium is initially dissolved in the
centre of the cabinet, near the brine
pipe
18
Remedy
Check blending valve and mixing ratio
Fault "too much water in the storage
tank"
Check blending valve and mixing ratio
Clean brine tube
Replace nozzles (fitter, CS*)
Chapter 7.5)
Clean or replace the pipework
Clean control valve or, if necessary, re-
place control head (CS*)
Clean and, if necessary, replace water
meter (CS*)
Exchange resin (CS*)
Clean brine tube
Clean and, if necessary, replace drain
tube
Clean and, if necessary, replace brine
valve (CS*)
Pour a cup of hot water over the lumps
and keep stirring, until all lumps have
disappeared
Reset the clock (has no effect on the
function)
Before refilling, move the undissolved
magnesium to the middle of the cabi-
net, using a spoon or similar. Then fill in
new magnesium salt
Correct the position of the control orifi-
ce or replace the complete adapter.
MU1H-1413GE23 R1106