Intended Use; Testers Information; Device Elements; Display Elements - Nieaf-Smitt EazyVolt Basic Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

The tester may be opened by an authorized service
technician only.
5.1
The tester may be used only under the conditions and
for the purposes for which it was designed. Therefore,
observe in particular the safety instructions, the techni-
cal data including environmental conditions.
6
6.1
1.
Test probe -
2.
LED-indication
3.
Test tip +
6.2
1.
Single Pole Test; ELV Warning
2.
Voltage indication
3.
LEDs indicating 12 V and polarity
4.
Buzzer/Continuity LED
7
7.1
The tester switches on when it detects shorten
tips, or an AC or DC voltage above approx. 10 V or
a live phase on + (single pole test).
7.2
Connect both probes to the object under test.
The voltage is indicated by LEDs
- Buzzer sounds when a threshold voltage is
50 VAC/DC
Voltage polarity is indicated in following manner:
-
AC: + and -12 V LED are both on
- +DC: +12 V LED is on
- - DC: -12 V LED is on
Once the tester is powered on, it will automatically
measure voltage in the range of 12 V - 690 V.
When the L2 probe + is the positive (negative)
potential, the Polarity indication LED indicates
'+DC' ('-DC').
In case of empty batteries,
±12/24/50/120/230/400/690V LEDs still indicate
the presence of voltage
7.3
Make sure the object under test isn't live
Connect both test probes to the object under test.
- Continuity test performed automatically
- Buzzer/Continuity LED lights up and buzzer
sounds continuously to indicate continuity.

Intended Use

Testers Information

Device elements (

Display elements (

Preparation for tests

Auto-power-on/ switching on

Voltage test (

Continuity test (

on page 3)
on page 3)
and
on page 3&4)
on page 4)