Lenze 9400 E94 MHE Série Instructions De Montage page 62

Table des Matières

Publicité

4
Technical data
General data and operating conditions
Mounting conditions
Mounting place
Mounting position
Clearance
above/beneath
at the side
Supply conditions "Single Drive"
AC mains operation
DC−bus operation
Power systems
TT
TN
IT
Motors
Environmental conditions
Climate
Storage
Transport
Operation
Site altitude
Pollution
Vibration resistance
Transport
Operation
62
EN 60034
IEC/EN 60721−3−1
IEC/EN 60721−3−2
IEC/EN 60721−3−3
EN 61800−5−1
2
(9.81 m/s
= 1 g)
IEC/EN 60721−3−2
EN 61800−2
Germanischer Lloyd
IEC/EN 60068−2−6
l
in the control cabinet
vertical
Comply with the device−relating mounting instructions.
Can be installed in a row without any clearance
No direct connection, DC supply module or "Single Drive"
network required
Direct connection via terminals or busbars
For more information, please see the chapter DC−bus
operation.
Operation allowed without restrictions.
Additional device−internal measure required (see mounting
instructions for the installation backplane, "Earthing of
internal EMC filters" chapter)
Only use motors that are suitable for inverter operation.
Insulation strength: max. û ³ 1.5 kV, max. du/dt ³ 5 kV/ms
1K3 (−25 ... +60 °C)
2K3 (−25 ... +70 °C)
3K3 (−10 ... +55 °C)
Current derating from +45 ... +55 °C: 2.5 %/°C
0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Degree of pollution 2
2M2
2 ... 9 Hz: Amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
200 ... 500 Hz: acceleration resistant up to 15 m/s
5 ... 13.2 Hz: Amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
10 ... 57 Hz: Amplitude 0.075 mm
57 ... 150 Hz: Acceleration resistant up to 1 g
2
2
EDK94AMH24 DE/EN/FR/ES/IT 6.0

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E94 she single drive highline sérieE94 she single drive stateline série

Table des Matières