Checking the correct position
The device is ready to use for testing when the touch elec-
trode is touched and the lamp GL1 lights up. If it doesn't,
either the device has been incorrectly inserted or the socket
outlet has been incorrectly wired. Rotate the Schuki I 180°,
then re-insert into the socket and re-check the positioning.
No fault determined
Figure 2: All lamps in the middle row light up. The lamp GL1
must light up when the touch electrode is touched.
You must observe the fault depicted in figure 9.
Fault indication
No current flowing
None of the lamps light up. Touch the touch electrode as well.
Should none of the lamps light up, the phase conductor is not
connected.
If one of the lamps in the middle row glows, then the phase
conductor is connected to the respective connection.
Device plugged incorrectly
Figure 3: The lamps N, L1 and L2 light up. When the touch
electrode is touched, the lamp GL1 does not light up.
The phase conductor is not contacting the left-hand pin of the
test device (viewed when device is inserted and faceplate visi-
ble); it cannot be tested. Rotate the Schuki I 180° and re-
insert.
12
No neutral conductor
Figure 4: The lamps L1 and PE light up. GL1 lights up when
the touch electrode is touched.
You must observe the fault depicted in figure 5.
No neutral conductor, phase and protective
earth have been reversed.
Figure 5: The lamps L1 and PE light up. Touching the touch
electrode has no effect.
The phase conductor is connected to the earthing contact!
No protective earth
Figure 6: The lamps L1 and N light up. GL1 lights up when the
touch electrode is touched.
13