Self Test & Charging
Test button
A short press will run FT(func�on test).
Duration Test
A full rated dura�on test is carried out which interval
and shedule are controlled by Interact system.
LED indication
Solid Green
Fast Flashing
Slow Flashing
Alternate Flashing
Red/Green
1. Blink LED-channel from ba�ery power at 0.5Hz, 50% duty-cycle, Fade-�me=zero
alterna�ng
2. Red/green LED Indicator alterna�ng
Red/Green
Reset mode; Emergency mode; Extended emergency mode
off
A 5-second func�on test is carried out and the interval
and schedule are controlled by Interact system.
The ba�ery will begin to charge when its voltage reduce to
a designed figure. The charging will be finished in 24 hours.
LED Green ON
LED Red ON
Device is OK
Func�on Test
Dura�on Test
Inhibit Mode
4/8
5
Function Test
SECONDS
Charging Time
24H
LED Off
Fast Flashing
Slow Flashing
Fast, 0.1s
Slow, 1s
Very slow, 4s
Solid Red
Device Fault
LED Driver Fault
Ba�ery Fault