Functional description

The communication module is used to connect the FPA-5000 fire panel to the parent UGM 2020
security system.
The module provides two bi-directional transmission paths.

Terminal assignment

Pos.
Labelling
1
SDI 1 +
2
SDI 1 -
3
SDO 1 +
4
SDO 1 -
5
SDI 2 +
6
SDI 2 -
7
SDO 2 +
8
SDO 2 -

Technical specifications

Operating and display elements
Input voltage
Maximum current consumption
- Standby operation
- One transmission path active
- Both transmission paths active
Maximum line length
Maximum line resistance
Baud rate
Protection class
Safety class
EMC immunity
EMC emission
Permissible operating temperature
Permissible storage temperature
Permissible relative humidity
Housing material and colour
Dimensions (h x w x d)
Weight
Product description FPE-5000-UGM
Connection
Data input +
Data input -
Transmission
Transmission
path 1
Data output +
Data output -
Data input +
Data input -
Transmission
Transmission
path 2
Data output +
Data output -
4 bi-colour LEDs (green = transmission / yellow = fault)
1 key (LED test)
20 V DC–30 V DC (min–max) / 5 V DC ±5 %
7 mA (at 24 V DC)
10 mA (at 24 V DC)
13 mA (at 24 V DC)
1000 m
70 Ω
9600 bit/s for 1000 m – . . 38400 bit/s for 200 m
IP 30 / EN 60529
II in accordance with IEC 60950 / EN 60950
EN 50130-4 / FCC Part 15
EN 61000-6-3 / FCC Part 15
-5 _C . . . 50 _C
-20 _C . . . 60 _C
max. 95%, non-condensing
ABS plastic (UL94 V-0), satin finish, anthracite, RAL 7016
approx. 110 x 90 x 60 mm
approx. 150 g
1 2
13 / 32
F.01U.028.289
3 4
5
6
7
8
BDL-F01U028306 / A3
ST - FIR / PRM1 / deh