5.0 Controls
(continued...)
Installer's Set-up Parameters
To access the installation parameters menu, scroll to AUTO
(while in full mode), then press (OK) for 10s. Use (
keys to highlight the parameter to be adjusted. Press (OK) to
toggle the parameter setting, when the value starts to blink, use
Parameter
Name
dEG
Select temperature scale.
00:00
Select the hour format.
AIr
Calibration of the internal air sensor against the actual
(Air)
room temperature.
(The calibration must be done after 12 hours working
at the same set temperature).
CSP
Cooling set point.
HSP
Heating set point.
AiPu
The air pulse will operate 5 minutes on the 5 minutes
off to ensure effective air circulation in cooling.
Nb vAL
Selection of the number of valves to be driven.
(2 Pipe
This parameter depends on the system design.
models only)
FAS SPEE
Allows the maximum fan speed to be switched off -
the unit will only run in Low and Medium speeds.
NIGt
Select option for fan speeds when the unit reverts to
night set back in cooling operation.
CLr ALL
Reverts the control back to factory settings.
End
Exit the installation menu.
Program Mode
Built-in Program Selection
A quantity of 9 built-in (P1-P9) and 4 user defined (U1-U4) timed
program options are available to choose from. Each day is
divided into 24 one hour periods operating in either Comfort
setting (21°C default) or Night set-back setting (19°C default).
Built-in programs description
P1 Morning, Evening & Weekend
P2 Morning, Afternoon, Evening
& Weekend
P3 Day & Weekend
) and (
)
Description
P4 Evening & Weekend
P5 Morning, Evening
P6 Morning, Afternoon & Weekend
P7 7h-19h (Office)
the (+) and (-) keys to adjust the value. Then, press (OK) to
confirm. Once parameters are set, go to <End> parameter and
press (OK) to go back to the main menu.
Default Setting
°C
12H
To adjust the air sensor temperature, enter the
measured temperature using the (-) or (+) keys.
To confirm the calibration, press (ok)
Press (+) and (-) keys at the same time to reset
the offset value.
The default water switching temperature for cooling
is 15oC, this can be altered by pressing (+) or (-) keys
then pressing (ok) to confirm.
The default water switching temperature for heating
is 32oC, this can be altered by pressing (+) or (-) keys
then pressing (ok) to confirm.
YE5
(Yes)
0 valve
FA5
For Fast
NOr
(For Normal regulation)
Press (OK) for 5 seconds
Scroll to the preferred program number P1-P9 (FIG 9, A) using
the (+) and (-) keys. The controls will then automatically go back
to AUTO mode.
P8 8h-19h, Saturday
P9 Weekend only
Alternative Setting
°F
24H
NO
(No)
1 valve
NEd
For Medium
AL1
(Fan speed 1 only)
Press (OK)
EN