Safety Rules; Conformity To Standards - Scame Rocker-Ex Serie Installation, Utilisation Et Entretien

Table des Matières
Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 17
THIS DOCUMENT SHOULD BE READ CAREFULLY BEFORE INSTALLATION
Recipients: expert electricians or duly trained personnel.
1. INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR SAFE USE

1.1 SAFETY RULES

The ROCKER-EX[GD] Light Switch are designed as Group II Category 2 equipment and is suitable for
use for fixed installation in areas with explosion hazard designated Zone 1 / Zone 21. These operating
instructions must be kept in safe place for later consultation. Use ROCKER-EX[GD] Light Switch only for
their intended duty in the undamaged and clean condition, and only where the resistance of the material
to the surroundings is assured. No modifications are allowed to the ROCKER-EX[GD] Light Switch and
the flameproof joints are not intended to be repair.

1.2 CONFORMITY TO STANDARDS

• EN 60079-0: 2012/A11:2013
• EN 60079-1:2014
• EN 60079-7:2015+A1:2018
• EN 60079-31:2014
• IEC 60079-0:2017
• IEC 60079-1:2014
• IEC 60079-7:2015
• IEC 60079-31:2013
They are manufactured and tested in accordance with ATEX directive 2014/34/EU, and IECEx certification
scheme, state-of-the-art engineering practice and ISO 9001.
2. TECHNICAL DATA
Marking acc. to 2014/34/EC:
Explosion Protection Type:
EC type examination certificate:
Rated voltage:
Rated current:
Ambient Temperature range:
Perm. storage temperature in original packing: -50°C ≤ Ta ≤ +80°C
Protection Degree
II 2 GD
Ex db eb IIC T6 Gb (with Tamb +40°C)
Ex db eb IIC T4 Gb (with Tamb +60°C) ; Tcable = 85°C
Ex tb IIIC T 80°C Db
INERIS 19 ATEX 0014X
IECEx INE 19.0012X
Max. 250V; 50/60 Hz
Max. 16AX
-50°C ≤ Ta ≤ +60°C
-35°C ≤ Ta ≤ +60°C
IP66