Télécharger Imprimer la page

Technical Characteristics - hager HTG410H Manuel Utilisateur

Masquer les pouces Voir aussi pour HTG410H:

Publicité

Les langues disponibles

Les langues disponibles

Z
The HTG410H is a multi-energy data logger
and server. The HTG411H version is delivered
additionally with a 4GB micro SD card. It is
intended to configure systems and products,
collect, store and time stamp information for
connected products. It processes this information
and monitors the quality of the electrical distribution
and makes it available to the user through an
embedded webserver. This product is accessible
from the Internet network.
Prerequisite for installation:
Equipment:
- a computer with internet browser
(Chrome recommended),
- an RJ45 Ethernet cable.
In case of an extended Ethernet network:
- an Ethernet network socket,
- product name on the network,
- a static or dynamic IP address,
- the network mask.
This device is to be installed only by a
professional electrician fitter according to
local applicable installation standards.
Do not install this module outside the
building.
Power supply over Ethernet (PoE)
prohibited.
In "Setup ON" mode, the HTG410H
activates its DHCP server on "Setup -
Ethernet 1" port.
Front face and connections
Output relay
Digital input
Digital input
24 V s SELV
HTG410H
Setup
Setup (1)
ON
Selector
OFF
LED
Modbus
RS485
Termination
resistor
120
Modbus RS485 (2)
LED information
LED
Colour
Power
Green
Green
or orange
Red
Red or orange Fixed
Modbus
Green
RS485 /
Ethernet 1 /
Ethernet 2
Red
2
Installation
The HTG410H / HTG411H must be fitted on a DIN
rail.
Implementation
1. Connect the inputs / outputs on the HTG410H /
HTG411H terminal block.
2. Connect the Modbus and Ethernet networks as
appropriate.
3. Enable 120 Ω termination resistor (selector (2) to
set to «ON») if the product is fitted at the end of the
Modbus network.
4. Check that the selector «Setup» (1) is in «OFF»
position.
5. Connect the 24 V s power supply (SELV).
First configuration
1. Start the software update:
a) download the latest software version from http://
hgr.io/r/htg410h or http://hgr.io/r/htg411h
b) unzip the downloaded file
c) read the file «readme.txt»
2. Connect the computer to the RJ45
«Setup - Ehernet 1» connector of HTG410H /
HTG411H using the Ethernet cable.
3. Turn switch «Setup» (1) in «ON» position.
4. Perform a reset by switching the power
supply off and again on.
5. Activate the Web browser on the computer.
6. Enter: url : https://192.168.0.1
7. Setting the HTG410H / HTG411H, refer to the user
guide, downloadable from http://hgr.io/r/htg410h
or http://hgr.io/r/htg411h website or with the
Datamatrix scanning.
Digital
Input 1
Input 2
Output
O
O
ut utp
p
u
u
t
t
Output
Input
0-10 V
PT100
Digital
Di Dig
g
it ita
a
l
l
Modbus
6 0
6 0
State
Status
Fixed
Functional product.
Blinking
Product initialisation.
Blinking
Product enters in power reserve.
Software startup problem.
Off
Product not powered.
Fixed / blinking
Connected and functional network.
Off
No communication network detected.
Fixed / blinking
Communication fault.
login : admin
password : admin
Analog
0 - 10 V output
PT 100 input
4 - 20 mA input
4 - 20 mA input
LED
Input 1 Input 2
4-20 mA
Analog
Ethernet 1
Ethernet 2
Power ON
USB 2.0
Solution
/
Wait for initialisation.
If the indication remains, refer to manual.
Wait during the shutdown progress.
Perform a reset by switching the power supply off.
Wait for LED to switch off before switching the power supply on.
If the indication remains, refer to manual.
Check the power supply.
/
Check the connection.
Check the configuration of links.

Technical characteristics

External safety extra low
voltage power supply
Typical consumption
Ethernet network
com munication
Modbus network
com munication
Operating temperature
Storage temperature
Humidity storage
Binary digital input 1 and 2
Analog input
4 - 20 mA 1 and 2
PT 100 input
Binary digital output
Number of relay cycles
Analog output 0 - 10 V
Power supply, digital inputs,
digital output connection
Analog inputs, analog
output connection
Degree of protection
Weight
Maximum operating altitude
Micro SD card
USB port 1
(front face)
USB port 2
(under the product)
*: The use of product at the maximal temperature can reduce its life expectancy.
Setup
1
Modbus RS485
8
1
2
3
4
5
Micro SD memory card slot
1
RJ45 port Modbus RS485
2
pin4: D1 or B/B' or "+" / green wire
pin5: D0 or A/A' or "-" / yellow wire
pin8: Common or C/C' or 0VL / brown wire
Not used
3
USB 2.0
4
RJ45 Setup port - Ethernet 1
5
RJ45 port - Ethernet 2
6
I
mportant: The RS485 Modbus circuits must be connected only
to external RS485 Modbus circuits that are Safety Extra-Low
Voltage (SELV).
24 V s
(SELV)
+/- 10 %
7 VA
Ethernet - TCP / IP -
RJ45 / 100 base - T /
IEEE 802.3
RS485 Modbus RJ45
-25° to +70°C*
-55° to +85°C
95% max HR at 55°C
15 to 27 V s
Input impedance
<300 Ohms
2-wire probe -
EN 60751 compliance
5 to 30 V s / v 10 mA to 3 A
resistive dry contact
100000
Min impedance
>= 1 kOhms
0.75 - 2.5 mm²
0.2 - 1.5 mm²
IP 20
290 g
2 000 m
Class 10
USB 2.0 Type A
standard connector
USB 2.0 Type A
standard connector
1
2
6
6LE007311A

Publicité

loading

Ce manuel est également adapté pour:

Htg411h