Eaton CROUSE-HINDS GHG 627 7 R Série Mode D'emploi page 5

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

D1
UVAR
D2
1.3
Undervoltage release (UVAR)
Typ: GHG627 7 ...
Rated control voltage (U
):
s
AC 50 / 60 Hz
Operating range:
Drop-out voltage
x U
s
Pull-in voltage
x U
s
Power consumption:
AC
Pull-in power
Holding power
Max. opening time:
Minimum command time:
C1
SR
C2
1.4
Shunt release (SR)
Typ: GHG627 7 ...
Rated control voltage (U
):
s
AC 50 / 60 Hz
Frequency range:
Operating range:
AC 50 / 60 Hz
x U
s
Power consumption:
AC
Pull-in power
Holding power
Max. opening time:
Minimum command time:
Explosion-protected circuit breakers, series GHG 627 7 .. R....
R 0 ...
24 ... 480 V
0,35 ... 0,7
0,85 ... 1,1
1,5 VA
1,5 VA
19 ms
10 - 15 ms
R 0 ...
12 ... 480 V
0 ... 400 Hz
0,7 ... 1,1
2,5 VA / W
2,5 VA / W
20 ms
10 - 15 ms