FS-555
The FS-555 and FS-555C occupancy sensors turn lighting ON and OFF based on occupancy. The sensors use ultrasonic sensing
technology. Once the space is vacant and the time delay elapses (adjustable from 5 to 30 minutes), lights will turn OFF.
The FS-555 and FS-555C occupancy sensors operate at120/277 VAC and are designed for installation in a light fixture.
The load turns ON within 5 seconds when power is applied to the sensor.
The FS-555 (no cones) is designed for use in wall-mounted lighting
fixtures where the transducers face away from the wall at an angle of
approximately 20
from vertical. It is particularly well suited for use in
o
stairwell applications as well as in other wall mount applications.
The FS-555C includes directional cones over the transducers.
The FS-555C is designed for use in hanging light fixtures where the cones
face downward over the coverage area. This gives the FS-555C a large
rectangular shaped coverage pattern.
FS-555C
DESCRIPTION AND OPERATION
Wattstopper
40 kHz Ultrasonic Occupancy Sensor
Line Voltage · Ceiling/Wall Fixture Mount
Tension de ligne du détecteur de présence à ultrasons 40 kHz ·
Fixation dans un luminaire au plafond/mural
Sensor de ocupación ultrasónico de 40 kHz
voltaje de línea • Montaje en soporte para pared cielorraso
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Power
Voltage .................................................... 120/277VAC 50/60Hz
Power Consumption .........standby 0.4W, active 1W @ 120 VAC
......................................standby 0.6W, active 1.2W @ 277 VAC
Load Ratings
................. 120/277VAC, 4.9A (N.O.), E-Ballast, Tungsten, CFL
.................................................................. 4.9A(N.C.), Tungsten
....................................5A (N.O.), 5A (N.C.), Ballast, LED Driver
Motor ......................................................... 120/277VAC, 1/10 hp
Time Delay Adjustments ................................. 5, 10, 15 or 30 minutes
Test Mode .............................. 5 second time delay for 5 minutes
Sensitivity Adjustments .........................................................Min~ Max
FS-555 coverage ..................... @ 8' height at 20
................................ 23' min. linear, 10' min. at 90
FS-555C coverage ................................ @ 10' height parallel to floor
..........................................................12' min. radius from center
Operating Temperature ............................ . .32° to 131°F (0° to 55°C)
Dimensions (see template)
Body ........5.19" x 1.27" x 1.64" (131.8mm x 32.3mm x 41.7mm)
Mounting base ...................... 6.11" x 1.27" (155.2mm x 32.3mm)
Mounting hole centers ..........5.75" x 0.79" (145.3mm x 20.1mm)
APPLICATIONS
Figure 1a.
Figure 1b.
®
SPECIFICATIONS
o
angle from vertical
on each side
o

Publicité

loading

Sommaire des Matières pour LEGRAND Wattstopper FS-555

  • Page 5 INSTRUCTIONS EN FRANÇAIS DESCRIPTION ET FONCTIONNEMENT CARACTÉRISTIQUES Les détecteurs de présence FS-555 et FS-555C allument Alimentation et éteignent la lumière en fonction de la présence Tension ................ 120/277 VCA, 50/60 Hz détectée ou non. Les détecteurs utilisent une technologie Consommation électrique ......Veille 0.4 W, actif 1 W à 120 VCA de détection par ultrasons.
  • Page 6 INSTALLATION 1. Consultez les schémas 4, 5 et 9 pour déterminer le câblage de charge AVERTISSEMENT : COUPER LE qui convient pour le FS-555 et les réglages de l’interrupteur de mode COURANT AU DISJONCTEUR PRINCIPAL de présence du détecteur. AVANT D’INSTALLER LE CÂBLAGE. 2.
  • Page 7 Vue de dessus, couverture du FS-555C, Vue de dessus, couverture du FS-555, détecteur fixé à 2,43 m (8 pi) du sol détecteur fixé à20 par rapport à la verticale Schéma 7. Schéma 6. RÉGLAGE DU DÉTECTEUR Avant de procéder aux réglages, installez les meubles, activez les circuits d’éclairage et mettez les systèmes CVCA en position neutralisé/marche.
  • Page 8 BOUTON DU MODE TEST Ce bouton permet de choisir le mode de fonctionnement du FS-555. • Une pression momentanée déclenche le mode test. • Appuyez sur le bouton et maintenez-le enfoncé pendant 5 secondes pour déclencher le mode de rodage de la lampe. •...

Ce manuel est également adapté pour:

Wattstopper fs-555c