9. Specifications
9. Specifications
General
EN
Measurement principle
Measuring range
Nominal size of the
optical display
Self-indication in case of
malfunction
Product label
Accessories
Accuracy
Switching accuracy
-1 ... +5 bar at 20 °C
-1 ... +9 bar at 20 °C
-1 ... +11.5 bar at 20 °C
Indication accuracy on numbered scale
-1 ... +5 bar at 20 °C
-1 ... +9 bar at 20 °C
-1 ... +11.5 bar at 20 °C
24
Reference gas measurement
0 ... 10 bar abs. at 20 °C SF₆ gas
■
0 ... 12.5 bar abs. at 20 °C SF₆ gas
■
100 mm
Integrated into the instrument, the switch contact is actuated in
case of leakage in the reference chamber
Lasered onto the reference chamber, maximum weather resistance
See model GLTC-CV
±70 mbar at calibration pressure at 20 °C, gaseous phase
■
±100 mbar at calibration pressure at -30 ... +50 °C, gaseous
■
phase
±100 mbar at calibration pressure at 20 °C, gaseous phase
■
±150 mbar at calibration pressure at -30 ... +50 °C, gaseous
■
phase
±150 mbar at calibration pressure at 20 °C, gaseous phase
■
±200 mbar at calibration pressure at -30 ... +50 °C, gaseous
■
phase
±70 mbar at calibration pressure at 20 °C, gaseous phase
■
±100 mbar at calibration pressure at -30 ... +50 °C, gaseous
■
phase
±100 mbar at calibration pressure at 20 °C, gaseous phase
■
±150 mbar at calibration pressure at -30 ... +50 °C, gaseous
■
phase
±150 mbar at calibration pressure at 20 °C, gaseous phase
■
±200 mbar at calibration pressure at -30 ... +50 °C, gaseous
■
phase
Calibration pressure established by means of reference isochore,
generated by Prof. Bier
WIKA operating instructions, model GDM-RC-100