Télécharger Imprimer la page

D+H ZA 85 Mode D'emploi page 6

Masquer les pouces Voir aussi pour ZA 85:

Publicité

Les langues disponibles

Les langues disponibles

Technical data
Type
Power supply
Nominal current
Nominal force
Nominal locking force
Service time
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Emission sound pressure level LpA ≤ 70 dB(A)
Nominal stroke length* / **
Additional functions **
* Adjustable with PLP 1
Normal operation =
SHEV- fast running =
Forces
ZA 35
ZA 85
OPEN
300 N
800 N
CR III
300 N
800 N
CR II
300 N
800 N
CR I
300 N
800 N
Closing edge protection
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive protection. The
closing speed in closure Range 2 and 1 is reduced to
5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
6/16
ZA 35/85/105/155
ZA 35 (-HS)
24 V DC, ±15%
0,5 A (1,2 A)
300 N
1100 N
>20 000 double strokes
30 % (With cycle time 10 minutes)
Aluminium powder-coated (~RAL 9006), polycarbonate
IP 65 ("-W" = IP 54)
-5 ... +75°C
30 min / 300°C
See type plate
Closing edge protection activated (3 stroke repeatings)
** Programmable with PLP 1 and SCS
ZA 105 ZA 155
1000 N
1500 N
All forces
1000 N
1000 N
1000 N
1000 N
+ approx. 20 % switch-off reserve
800 N
800 N
(temporary)
ZA 85 (-HS)
ZA 105 (-HS)
24 V DC, ±15%
24 V DC, ±15%
1,0 A (2,0 A)
1,2 A (2,2 A)
800 N
1000 N
Running speed and forces
Main closing edge
English
ZA 155 (-HS)
24 V DC, ±15%
1,4 A (2,5 A)
1500 N
99.824.29 1.4/04/16

Publicité

loading

Ce manuel est également adapté pour:

Za 35Za 105Za 155