NOTES: DO NOT TAMPER WITH THE FLOAT SWITCH. THE NON RESPECT OF THE
FOLLOWING POINTS WILL AUTOMATICALY CAUSE THE CANCELLATION OF THE
WARANTY OF THE PRODUCT
• Before any operation on the float remember to disconnect the power supply from the
main power.
• Check that the maximum motor power does not exceed the float's electrical values.
• in case of cable damage by the final user or installer, the float must be replaced.
• Do not make any joint on the cable of the float switch, as immersion of such joints
could cause short circuits or electrical shocks.
TECHNICAL FEATURES:
• AC: Max 10A (250V) resistive load - 8A (250V) motor load
Min 1200mW (12V/100mA)
BREAKING CAPACITY DC1: 6 A - 30 V DC
• Operating temperature: max. +50°C (+40°C ACS)
• Wire gauge: 8,8mm (0.35in)
• Max depth: 40m
• Protection Grade: IP68
TERMINAL CONNECTIONS:
The upstream circuit must protect the electric wires from the overcurrent. WARNING: lack
of protection shall null and void the warrany in the event the float breaks.
72.A1-XX00 (PVC) – 72.A1-XX01 (H07 RN-F): double function (the fitter can choose the
emptying Fig.2 or filling Fig.3 when installing):
• Emptying: (Fig.2) when black and brown wires are used, the circuit opens when float is
down and closes when the float is up. Note: the blue/grey wire must be insulated.
• Filling: (Fig.3) when black and blue/grey wires are used, the circuit closes when float is
down and opens when the float is up. Note: the brown wire must be insulated.
Fig.2 emptying
ENGLISH
Activation angle: 45°
Fig.3 filling