EN: Installation Sheet
Description
The NC Series Intelligent Conventional Manual Call Point is
designed for indoor use with compatible conventional fire
panels. Each unit includes a built-in resistor (0, 100, 470, or
560Ω, depending on the model purchased).
All units are supplied with a resettable element – this can be
replaced with a breakable element, if required (order number
N-MC-FE). See "Replacing the resettable element" on page 3.
The series includes the following models.
Model
Description
NC-MC-0-R
Red intelligent conventional manual call point –
0Ω [1]
NC-MC-100-R
Red intelligent conventional manual call point –
100Ω
Red intelligent conventional manual call point –
NC-MC-470-R
470Ω
NC-MC-560-R
Red intelligent conventional manual call point –
560Ω [2]
Red intelligent conventional intrinsically safe
NC-MC-IS-0-R
manual call point – 0Ω
[1] Also available in blue (NC-MC-0-U), green (NC-MC-0-G), orange
(NC-MC-0-O), white (NC-MC-0-W), and yellow (NC-MC-0-Y).
[2] Also available in blue (NC-MC-560-U).
Figures
Figure 1: Backbox and mounting holes
Figure 2: Front assembly terminal block
Figure 3: Unlocking the front cover
Figure 4: Removing the front cover
Figure 5: Removing the resettable element
Figure 6: Replacing the front cover
Installation
Caution:
This product must be installed and maintained by
qualified personnel adhering to all local or national installation
requirements and any other applicable regulations.
The manual call point can be surface mounted or recess
mounted.
For surface mounting, order one of the backboxes shown in
the table below.
Model
Description
N-MC-BB-R
Red backbox
N-MC-BB-U
Blue backbox
N-MC-BB-G
Green backbox
N-MC-BB-O
Orange backbox
2 / 17
www.acornfiresecurity.com
Model
N-MC-BB-W
N-MC-BB-Y
For recess mounting, order one of the recess adaptors shown
in the table below.
Model
N-MC-AFM-R
N-MC-AFMG-R
N-MC-AFM-G
Remember to remove the protective dust cover before
installation.
Note:
The dust cover may also be used to indicate when the
unit is not operational (for example, before commissioning,
during maintenance, when disabled, etc.)
To surface mount the manual call point:
1.
Fix the backbox onto the wall using 4 × M4 screws (not
supplied) and feed the zone cable through the selected
cable knockouts or through the rear of the backbox.
See Figure 1 for the location of the mounting holes.
2.
Connect zone cable and relay cable (if required) to the
supplied terminal block, and then plug the terminal block
into the PCB connector on the back of the front assembly
(see Figure 2).
Use the supplied cable link to test cable continuity during
installation.
See "Wiring" below for terminal block connections and
zone cable specifications.
3.
Unlock and remove the front cover, and then remove the
resettable element.
To unlock the front cover, insert the key and turn it
clockwise (two clicks), then pull the cover outwards from
the bottom to remove it (see Figure 3 and Figure 4).
To remove the resettable element, push the element up,
and then pull it out (see Figure 5).
4.
Fix the front assembly to the backbox using the 2 screws
supplied with the unit (located in the backbox).
5.
Replace the resettable element (or add the breakable
element, if required), and then replace the front cover (see
Figure 6).
Turn the key anticlockwise (two clicks) to lock the cover,
and then remove the key.
Finally, test the manual call point (see "Testing" on page 3).
Wiring
For optimal system performance, use 0.129 to 3.31 mm² (26 to
12 AWG) twisted-pair cable.
Colour
Wire the unit as described below. Observe the indicated
Red
polarity.
Blue
Green
Orange
www.acornfiresecurity.com
Description
White backbox
Yellow backbox
Description
Red recess adaptor
Red recess adaptor with fork grips
Green recess adaptor
P/N 03-0211-501-3000-02 • ISS 03DEC21
Colour
White
Yellow