RHEASREG
SW
Mechanical paddle flow monitor RHEASREG
monitoring of liquid and gaseous, non-aggressive media in pipes, hydraulic systems of ¾'' through ½'' to 8'' diameter. The flow sensor is used as a
flow controller or low water alarm, e. g. for pumps in oil and cooling circuits, cooling systems, evaporators, compressors and heat exchangers,
with brass or stainless-steel bodies.
TECHNICAL DATA
Switching capacity:
Contact:
Housing:
Housing dimensions:
Base body:
Screwed socket:
Paddle:
Cable connection:
Housing temperature:
Max. temperature of medium:
Electrical connection:
Protection class:
Protection type:
Standards:
FUNCTION
Monitor:
Installation:
Connecting diagram
COM NO NC
®
SW with switching output, in an impact-resistant plastic housing, with stainless-steel paddle, for flow
15 (8) A; 24...250 V AC,
at 24 V AC min. 150 mA
dustproof microswitch as potential-free
single-pole changeover contact
plastic, UV-resistant,
material polyamide, 30 % glass-globe reinforced,
colour traffic white (similar to RAL 9016)
108 x 70 x 73.5 mm (Thor 2)
galvanised steel
brass or stainless steel (see table)
stainless steel V4A (1.4401)
cable gland, plastic (M 20 x 1.5; with strain relief,
exchangeable, inner diameter 8 - 13 mm)
–40...+85 °C
+120 °C
2
0.14 - 1.5 mm
, via screw terminals
I (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, EMC directive 2014 ⁄ 30 ⁄ EU,
low-voltage directive 2014 ⁄ 35 ⁄ EU
Contact COM – NO (red – yellow) breaks when flow rate drops to the preset value.
Simultaneously, contact COM – NC (red - blue) closes and can be used as signal contact.
Device is factory-set to the minimum switch-off value,
which can be increased by turning the range adjusting screw clockwise.
vertical in horizontal pipes, tee R x'' according to DIN 2950,
min. smoothing distance = 5 x pipe diameter upstream and downstream of paddle
SW
V
6
Rev. Data - V18

Publicité

loading