Specifications and Accuracy
DVC-6 and DVC-10
Polarity: Automatic
Voltage Range: 12 to 600 Volts (AC or DC)
Internal Basic Load: 0.7 W at 600 V (approximate)
LED Threshold
LED
Min. V
12
48
30
120
70
208
150
240
215
277
250
347
300
480
400
600
510
Frequency Range: 0 to 70 Hz
Test Current: Less than 2 mA
Identifying Energized Conductor: 100 V to 600 V
Frequency Range: 50 to 70 Hz
Indication: Tone
Continuity Test: 0 to 1 MΩ
Test Current: 5 µA (approximate)
Indication: Tone
Diode Test:
Open Circuit Voltage: 1.75 V (approximate)
Test Current: 10 µA (approximate)
Note: The fixed probe is positive when checking diodes and continuity.
GFCI Test:
Test Current: 6 mA ±10% at 120 V
Impedance: 20 KΩ nominal
Maximum Test Time: 30 seconds
Recovery Time: 10 minutes
Internal Load: 0.7 W @ 120 V
10
Max. V
10
40
100
180
220
265
330
450
570