RATINGS:
Voltage: 24 VDC
Current Consumption: 20 mA
Power Supply: IOS-PP24 Power Pack
Adjustable Ambient Light Level: 10 fc to Daylight
Selectable Time Delay: 5 sec to 30 min (DIP switch)
Test Mode: 5 sec upon initial power-up
PIR Sensitivity Adjustment: 50% or 100% (DIP switch)
Ultrasonic Sensitivity Adjustment: 30% to 100%
Coverage - PIR: up to 1600 ft
(150
2
Ultrasonic: up to 1000 ft
Temperature Range: 32° F to 122 °F (0° C to 50° C)
DESCRIPTION:
The IOS-CMP-DT-LV 360° Dual Technology Low Voltage Occupancy Sensors control the load based on
occupancy and ambient light levels. It combines passive infrared (PIR) and ultrasonic technologies to
help avoid false triggering while increasing presence detection. Selectable modes allow the sensor to
turn load ON and hold it ON as long as either or both technologies detect occupancy. If no movement is
detected for a user-specified time of 5 seconds to 30 minutes, the load is turned OFF. The occupancy
sensor provides a 360° coverage pattern, up to 1600 ft
sensor.
MOUNTING THE SENSOR
NOTE: A junction box and screwdriver are needed to complete this procedure.
See Figure 4 for reference.
1. Make sure power is turned off at the main disconnect.
2. Look for small opening on periphery of cover. With the help of a flathead screwdriver, snap off front
cover. Next, remove mounting adaptor by opening tabs A & B as shown in Figure 4.
3. Attach mounting adaptor to junction box.
4. Observe these guidelines when mounting the sensor:
• The occupancy coverage area may be more or less than the sensing distances shown in Figure 1
due to potential coverage area obstacles, such as furniture or partitions.
• Place the sensor at least 4 to 6 feet (1,2 to 1,8m) away from air supply ducts to prevent false
activations.
• If you mount the sensor outside of 8 to 10 feet (2,4 to 3m) from the floor, it affects the coverage
pattern. Decreasing the mounting height decreases the sensor range and increases the sensitivity
to smaller motions. Mounting the sensor at heights more than 12 to 14 feet (3,7 to 4,3m) reduces
sensitivity.
• For coverage of large areas with multiple sensors, an overlap of 10 to 20% is recommended as
shown in Figure 2.
• Avoid placing the sensor directly in line with an open door through which it has a clear view out.
This may cause the sensor to detect people walking by the door.
5. Punch knockout on the junction box and insert the IOS-PP24 power pack nipple into the knockout.
6. Pull the low voltage wires from the power pack into the junction box, through the conduit knockout.
7. Connect the low voltage wires from the power pack to the appropriate wire on the occupancy
sensor. See table below for wire designations. Refer to Figure 3.
Wire from power pack
Red wire (+24 VDC)
Black wire (Common)
Blue wire
8. To connect multiple sensors (up to 6) to power pack, run the blue control out wire from the sensor
to the blue wire of the power pack.
9. Align and snap sensor onto mounting adaptor.
10. After setting adjustment, snap cover back onto sensor.
All manuals and user guides at all-guides.com
)
m2
(93
)
2
m2
(150
) for PIR and 1000 ft
2
m2
To Terminal on Occupancy Sensor
+24 VDC terminal
Common terminal
Control Out terminal
360˚ Dual Technology
Low Voltage Occupancy Sensor
With Light Level Feature
Risk of Fire or Electric Shock
WARNING
• Disconnect power at the circuit breaker(s) or fuses before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code
requirements.
• Use COPPER conductors ONLY.
• Indoor dry location use only.
• Do not exceed electrical ratings.
Figure 1
(93
) for Ultrasonic
2
m2
8 ft
(2.44m)
Typical
desk-top
level
Figure 2
Figure 3
Figure 4
PIR/Ultrasonic
20%
Ultrasonic
Overlap
PIR
Coverage
44 ft.
(13.4m)
Ultrasonic
Coverage
30 ft.
(9.14m)

Publicité

loading

Sommaire des Matières pour Intermatic IOS-CMP-DT-LV

  • Page 1 DESCRIPTION: Figure 1 The IOS-CMP-DT-LV 360° Dual Technology Low Voltage Occupancy Sensors control the load based on occupancy and ambient light levels. It combines passive infrared (PIR) and ultrasonic technologies to help avoid false triggering while increasing presence detection. Selectable modes allow the sensor to turn load ON and hold it ON as long as either or both technologies detect occupancy.
  • Page 2 LIMITED WARRANTY Warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.intermatic.com. This warranty is made by: Intermatic Incorporated, 1950 Innovation Way, Suite 300, Libertyville, IL 60048. For additional product or warranty information go to: http://www.Intermatic.com or call 815-675-7000.
  • Page 3 DESCRIPTION : Figure 1 Le détecteur d’occupation basse tension à technologie double 360˚ IOS-CMP-DT-LV commande le circuit de charge en fonction de l’occupation et des niveaux d’éclairage ambiant. Il combine des technologies à infrarouge passif (PIR) et à ultrasons pour éviter les faux déclenchements tout en améliorant la détection de présence. Les modes sélectionnables permettent au détecteur mettre le circuit de charge SOUS TENSION (ON) et à...
  • Page 4 Ce service de garantie est disponible (a) en retournant le produit au vendeur auprès duquel l’unité a été achetée ou (b) en remplissant un formulaire en ligne de réclamation de garantie sur www.intermatic.com. Cette garantie est faite par : Intermatic...
  • Page 5 DESCRIPCIÓN: Figura 1 Los sensores de ocupación de voltaje bajo con tecnología doble en 360° IOS-CMP-DT-LV controlan la carga según la ocupación y los niveles de luz ambiente. Combina tecnologías infrarroja pasiva (PIR) y ultrasónica para ayudar a evitar disparos falsos y aumentar la detección de presencia. Los modos seleccionables permiten que el sensor ENCIENDA la carga y la mantenga ENCENDIDA hasta que una o ambas tecnologías detecten ocupación.
  • Page 6 Este servicio de garantía está disponible mediante (a) la devolución del producto al proveedor al que se le compró la unidad; o (b) el llenado de una reclamación de garantía en línea en www.intermatic.com. Esta garantía la otorga: Intermatic Incorporated,...