Field Entry
Baseboard System
Mode
STGMODE
PID
BOIL TARGET
180(82)
OUTDR START
70(21)
OUTDR DSGN*
-10(-23)
BOIL START
70(21)
BOIL DSGN
180(82)
BOIL OUT MAX
182(83)
BOIL MAX
170(77)
BOIL MIN
140(60)
DLY
BOIL MASS
1
STG DLY
Au if PID in STGMODE
DIFF
Au if PID in STGMODE
STG DIFF
ON DLY
OFF DLY
MIN ON
MIN OFF
PUMP DELAY
Off
WWSD
65(18)
0˚ F
F or C
Set the "MODE" to 1 or 2 if an outdoor Sensor is not used (1 = parallel piping, 2 = primary/secondary piping)
Caution:
"Factory" position on dip switch has to be returned to "installer" position to prevent unauthorized changes to factory settings.
*Local design input may vary from the example shown. Be sure to use design inputs for your geographical location.
EXAMPLE SETTINGS MAY VARY ACCORDING TO ACTUAL DESIGN REQUIREMENTS.
8
EH-M3-40 Boiler Operation and Installation Instructions
Basic Monitron II and Minitron M3 Setup
Dual Temperatures are Fahrenheit (Celsius)
Field Entry Example for Mode 4 or Mode 5
Low Temp
System
4 or 5
4 or 5
P
P
180(82)
180(82)
70(21)
70(21)
-10(-23)
-10(-23)
70(21)
70(21)
180(82)
130(54)
182(83)
150(66)
170(77)
130(54)
140(60)
80(27)
No Entry
N/A
N/A
N/A
N/A
2(1)
2(1)
4(2)
4(2)
1:00
1:00
0:30
0:30
0:30
0:30
0:30
0:30
Off
Off
4 = Parallel Piping, 5 = Primary/Secondary Piping
This is for DHW setpoint demand - if used
May be -20(-29) or -30F(-34) depending on area design temp.
This is used in the calculation of slope
Radiant - 130(54) Wet, 140(60) or 150F(66) for Dry system
Default 182(83) - Use "FACTORY" Dip Switch to Adjust - DO NOT EXCEED THIS MAX
Default 180(82) - Use "FACTORY" Dip Switch to Adjust. Set same as BOIL DSGN
Default 140(60) - Use "FACTORY" Dip Switch to Adjust.
Note:Some heating equipment may require a minimum water temperature - ie fan coils
Not valid for Electric Boiler application
Minimum time between firing stages
1/2 differential around target temp
Temperature drop at which next stage turns on
Time before turning on next stage
Time before turning off next stage
Minimum time stage is on before allowed to go off
Minimum time stage is off before allowed to come on
Note