Communication
Power Supply
Bus cable
Bus current consumption
Control elements
Display elements
Measuring elements
Configuration elements
IR sensor range
Ambit of use
Operating temperature
Storage temperature
Relative humidity
Bus connection
Protection rating
Dimensions
Reference standards
Certification
TECHNICAL DATA
Bus KNX/EIB
By KNX/EIB, 29 V dc SELV bus
KNX/EIB TP1
5 mA max
1 mini programming key
1 red programming LED
1 green signal LED
1 PIR sensor (λ = 5÷14 μm)
1 twilight sensor (10÷500 lux)
1 rotating potentiometer to regulate the twilight
sensor,
1 rotating potentiometer to regulate the transmission
period
Max distance: 10m
Vertical range: 30° adjustable
Horizontal range: 105° adjustable
Indoors, dry places
-5 ÷ +45 °C
-25 ÷ +70 °C
Max 93% (no condensation)
2-pin Ø 1 mm plug connector
IP20
2 Chorus modules
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive 89/336/EEC
EN50428,EN50090-2-2
KNX/EIB