NOTE: If unit is located in or above a living
space, where damage may result from
condensate overflow, a field-supplied, external
condensate pan should be installed underneath
the entire unit, and a secondary condensate
line (with appropriate trap) should be run from
the unit into the pan. Any condensate in this
external condensate pan should be drained to
a noticeable place. As an alternative to using
an external condensate pan, some localities
may allow the running of a separate 3/4-inch
(19 mm) condensate line (with appropriate
trap) per local code to a place where the
condensate will be noticeable. The owner of
the structure must be informed that when
condensate flows from secondary drain or
external condensate pan, the unit requires
servicing or water damage will occur. To
further protect against water damage. install a
float switch to shut the unit off if the water in
the secondary pan gets too high.
CARE AND MAINTENANCE
To continue high performance and minimize possible equipment failure, it is essential that
periodic maintenance be performed on this equipment. Consult your local dealer as to the
proper frequency of maintenance, but it should be done at least annually.
The ability to properly perform maintenance on this equipment requires certain mechanical
skills and tools. If you do not possess these, contact your dealer for maintenance. The only
consumer service recommended or required is filter replacement or cleaning on a monthly
basis.
Page 12
Condensate Line
Trap
WASTE LINE CONNECTION
If the condensate line is to be connected to
a waste (sewer) line, an open trap must be
installed ahead of the waste line to
prevent escape of sewer gases.
CAUTION
environmental damage.
Air Gap Above Liquid Level
Sewer Line