ELC74
DIGITAL TIME SWITCH
SPECIFICATIONS
––––––––––––––––––––––––––––
Input Voltage: 24/120/208/240/277VAC, 50/60Hz,
10VA max. Output: SPDT, dry contact (unpowered).
WIRING INSTRUCTIONS & DIAGRAM
––––––––––––––––––––––––––––––
Use copper wire only. #12AWG or larger, suitable for
90°C (194°F). WIRING TO COMPLY WITH ALL
LOCAL AND NATIONAL ELECTRICAL CODES.
Bonding between conduit connection is not automatic
and must be provided as part of the installation. THE
ENCLOSURE MUST BE PROPERLY GROUNDED.
Minimum 20 lb. in. torque required at the terminals to
ensure proper connections.
LI-894(B)
CONTACT RATINGS
––––––––––––––––––––––––––––
LOAD
VOLTAGE
General
24/120-277VAC
Purpose
Ballast
120-277VAC
Tungsten
120-277VAC
120VAC
Motor Load
208-277VAC
Pilot Duty
120-240VAC
NOTE: Remove battery insulator before applying power to
insure memory carryover during power outage.
! CAUTION !
HAZARD OF ELECTRICAL SHOCK
Transformer core may be live. All power to this control must be
turned off at the main panel before installing or servicing.
REPLACE THIS INSULATOR AFTER WIRING OR SERVICING.
NSi Industries LLC • 888.500.4598 • www.nsiindustries.com
NSi Industries, LLC
TORK INSTRUCTIONS
p/n ELC74
LI-894(B)
7" X 4.5"
1C/0
3/2013
NO
NC
20A
15A
20A
20A
5A
1HP
1/4HP
2HP
1/2HP
470VA
275VA
LISTED
Enclosed Energy
Management
Equipment
4D64
CLASS 2
888.500.4598
www.nsiindustries.com

Publicité

loading

Sommaire des Matières pour NSi INDUSTRIES TORK ELC74

  • Page 1 Transformer core may be live. All power to this control must be turned off at the main panel before installing or servicing. REPLACE THIS INSULATOR AFTER WIRING OR SERVICING. 888.500.4598 LI-894(B) NSi Industries LLC • 888.500.4598 • www.nsiindustries.com www.nsiindustries.com NSi Industries, LLC TORK INSTRUCTIONS p/n ELC74 LI-894(B) 7”...
  • Page 2 MINUTERIE NUMÉRIQUE CAPACITÉ DES CONTACTS Schéma de principe –––––––––––––––––––––––––––– SPECIFICATIONS –––––––––––––––––––––––––––– CHARGE TENSION JAUNE CÂBLE NEUTRALISATION BLINDÉ Tension d’entrée : 24/120/208/240/277 V c.a., EXTERNE Usage général 24/120-277 V c.a. 20 A 15 A ROGUE 50/60 Hz, 10 VA max. CLASSE 2 NOIR JAUNE Sortie : contacts secs (ne sont pas sous tension),...