Télécharger Imprimer la page

AXMART VT+ Serie Manuel D'installation Et D'utilisation page 31

Publicité

Les langues disponibles

Les langues disponibles

Technical data: 1500 and 2400Nm models
Implantation
Materials
Sealing
Environment
Operating temperature
Operating altitude
Hygrometry
Pollution degree
Noise level
Weight
Mechanical data
Maximum torque
Operating time (90°)
Angular range
Duty cycle
Drive ISO5211
Manual control
Electrical data
Electric connection
Technology of motors
Voltages
1)
Overvoltage category
2)
Power
Rated current
Torque limiter
Number of feedback switches
Limit switches maximum voltage
Limit switches maximum current
Anticondensation heaters
1) The actuator tolerates voltage fluctuation of the electrical grid up to ± 10 % of its nominal system operating voltage
2) The actuator tolerates temporary overvoltages of the electrical grid
DSBA3600 • Rév. 04/03/2019
VT1500
 
Housing: Aluminium + EPOXY coating
Both inside and outside (wet environments possible)
maximum relative humidity 80% for temperatures up to 31°C decreasing linearly to
Applicable POLLUTION DEGREE of the intended environment is 2
1500Nm
155s
Secured handwheel without clutching system
3 x ISO M20 and specific multipin connector
100V to 240V AC 50/60Hz and 100V to 300V DC
24V to 48V AC 50/60Hz and 24V to 72V DC
TRANSIENT OVERVOLTAGES up to the levels of OVERVOLTAGE CATEGORY ll
4 to 250V AC/DC (Overvoltage category II)
 
Drive: Steel + Zn treatment
Shafts and screws : Stainless steel
IP68  
-20°C to +70°C  
Altitude up to 2000m
50% relative humidity at 40°C
(in most cases).
63db
57kg  
90° (180°-270° on request)
50%
Star 46 - F12/F14/F16
Brushless  
300W  
10 to 12A  
Electronic
2 (4 in option)
1mA to 5A max.
3 x 10W  
ENGLISH
UK
VT2400
2400Nm
210s
31

Publicité

loading

Ce manuel est également adapté pour:

Vt1500Vt2400Vt600Vt1000