Installation and operating instructions for geniovent.x 600 - 900 S
Notice de montage et mode d'emploi geniovent.x 600 - 900 S
Serial no.
Installation and operating instructions for up-
right, decentralised geniovent.x 600 - 900 S
ventilation units
Table of contents
1
Instructions, software, links ...............................
2
Safety ................................................................
3
Scope of delivery................................................
4
Intended use......................................................
5
Unit overview ....................................................
5.1
Functional description ................................
5.2
Product description.....................................
5.3
Unit variants................................................
5.4
System components....................................
6
Technical data....................................................
7
7.1
7.2
7.3
Connecting the air ducts .............................
7.4
7.5
Electrical connection...................................
7.5.1
Electrical terminal box ................
7.5.2
Connection cable ........................
EN
Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de
7.6
box (optional)...............................................
8
Commissioning ....................................................
8.1
Commissioning options................................ 4
8.2
8.3
Commissioning software.............................. 4
9
Cleaning, maintenance ........................................
9.1
Replacing the air filter.................................. 5
9.2
Cleaning unit ................................................
9.3
10 Special functions .................................................
10.1
Auto Sensor operation ................................. 5
10.2
Bypass ..........................................................
10.3
Frost protection strategies........................... 5
10.4
10.5
10.6
Switching test...............................................
10.7
10.8
Operation via app / web tool ....................... 6
10.9
Factory settings............................................ 6
12 EnOcean/KNX plug-in modules ............................
12.1
EnOcean components .................................. 7
12.2
KNX components.......................................... 7
1
13 Optional accessories............................................
1
13.1
Room air controls......................................... 7
1
13.2
Electric preheating register.......................... 7
1
13.3
1
13.4
External CO2 sensor..................................... 7
1
13.5
External VOC sensor..................................... 7
2
13.6
Motion sensor (PIR) ..................................... 7
2
13.7
Smoke gas switch......................................... 7
2
14 Spare parts ..........................................................
3
15 Service documentation........................................
3
Circuit diagrams / wiring plans ............................ 16
3
Product data sheets............................................. 17
3
3
Preface
3
Thank you for placing your trust in us and buying an AEREX
3
product. Our years of experience in ventilation technology
3
in buildings guarantees you a product of the very highest
quality. By opting for controlled ventilation with heat re-
3
4
covery you are actively improving your quality of life and
producing a better living environment in your building.
Heat recovery and the efficient use of energy help to pre-
4
serve the environment in the long term and save money.
We hope that this product brings you healthy air and much
happiness in living and working in rooms with controlled
ventilation.
5
1 Instructions, software, links
5
These instructions contain important information regard-
ing proper installation as well as information on how to op-
erate the ventilation unit. Installation only by qualified
5
electricians. These installation and operating instructions
and the wiring diagram (→ Electrical terminal box) form
5
part of every ventilation unit.
The Safety instructions supplement contains important in-
formation for the operator and specialist installer. Read it
carefully and completely, before operating, setting, open-
ing the ventilation unit or making changes to the ventila-
6
tion system. Follow the instructions.
Assemblies/components in the instructions are
not shown in their actual colours. Colours are used
to identify associated assemblies/components.
6
Commissioning software for configuring and adjusting the
7
ventilation unit → Commissioning [} 4] or
www.aerex.de.
7
2 Safety
• Read these instructions and the enclosed safety instruc-
tions carefully before installation.
• Follow the instructions.
• Pass these instructions on to the owner/operating com-
pany for safekeeping.
3 Scope of delivery
7
Ventilation unit with 3m mains connection cable, RB-ZF4
control panel (single control panel), approx. 3 m control
7
cable for RB-ZF4 and further connection cables e.g. USB,
Ethernet, approx. 3 m connection cable for external com-
ponents, these installation and operating instructions and
wiring diagrams.
When unpacking the unit, check to make sure
that the delivery is complete. Please contact the
dealer if any accessories are missing or if there has
been any damage in transit.
4 Intended use
This ventilation unit with heat recovery is used in central-
ised or decentralised ventilation systems. The unit
provides controlled ventilation and air extraction in, for ex-
ample, offices, school classrooms and other similar spaces.
They are floor-mounted units. Please note that the unit is
very heavy, weighing approx. 240 kg. The unit may only be
used if installed permanently, in dry indoor spaces and
with connected ventilation ducts. DN 315 connection. The
units do not have a unit switch. Scope for completely dis-
connecting the unit from the power supply should be
provided by the customer. The ventilation units are only
intended for domestic use and similar purposes. Any other
use or use that goes beyond this is considered improper
use.
5 Unit overview
When heat recovery units with enthalpy heat
exchangers are first installed, a slight odour may
be released over the first few weeks of operation.
This volatilises within a few weeks of operation.
5.1 Functional description
AEREX geniovent.x units make use of the principle of re-
covering heat and humidity (using special enthalpy heat
exchangers), which would otherwise escape outdoors
through open windows. The ventilation units direct the
warm exhaust air from the room via a cross-counterflow
heat exchanger or enthalpy heat exchanger and blow it
outside using an outgoing air fan. At the same time, an
outside air fan supplies the room with outside air, which
flows past the exhaust air in the heat exchanger, thereby
heating it. The ventilation unit is constructed such that
these two air flows do not mix. In order to reach the de-
sired setpoint temperature, the exhaust air can also bypass
the heat exchanger and be fed directly to the outgoing air
via the bypass shutter (summer-time, free cooling func-
tion). The optional electric supply air heat register can also
be used for heating to the desired comfortable supply air
temperature. To ensure the air quality in the living space
and to protect the system from potential contamination,
an exhaust air filter of class ePM10 60% (M5) and an out-
side air filter of class ePM1 55% (F7) are fitted on the in-
take side.
7185.1234.0003_RLF.9_02.23_AS
1

Publicité

Table des Matières
loading

Sommaire des Matières pour AEREX geniovent.x 600 S

  • Page 1: Table Des Matières

    By opting for controlled ventilation with heat re- 7.5.2 Connection cable ......7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 2: Product Description

    Degree of heat provision up to 95 %. Bypass Function: Used to bypass the heat exchanger. • Fans, with particularly energy-saving DC motors. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 3: Technical Data

    • USB cable with type B USB connector for commissioning of the unit. software run via laptop/PC. Length: approx. 0.5 m. Observe safety instructions. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 4: Installing The Geniovent.x 600-900 S Top Box (Optional)

    • the ventilation unit is correctly connected to the power supply and the cable lead-throughs are sealed. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 5: Cleaning, Maintenance

    8. Carefully slide the fully dried heat exchanger as far as it air, fixed factory setting), the supply air fan switches on will go into the housing. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 6: Switching Contact (Potential-Free)

    The actual room temperature is de- • Exhaust air / outgoing air fan termined using the selected temperature sensor. • Bypass shutter 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 7: Enocean/Knx Plug-In Modules

    (demand-controlled). The overrun time can be adjusted • Degree of protection: IP 00 (5...12...120 min). E093.1411.0000 Door, small, 900 S, cpl. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 8: Volume De Fourniture

    échangeur de chaleur à contre-cou- 7.5.1 Boîte à bornes électrique.... rant croisé ou un échangeur de chaleur enthalpique et 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 9: Description Du Produit

    Fonction : sert à dévier / raccorder les 4 conduits Ventilateur d'air extérieur d'air. • 4x raccords tubulaires DN 315 (geniovent.x 600 S, ge- Clapet de bypass niovent. X 900 S). 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 10: Caractéristiques Techniques

    • Température de service : 0° C à 40° C (tuyau dans le raccord d'air rejeté). • Type de protection : IP 20 selon EN 60529 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 11: Câble De Raccordement

    • tous les matériaux de protection (p. ex. de filtres à four- nir par le client) ont été retirés. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 12: Logiciel De Mise En Service

    4. Essuyer le bac à condensat. 7. Essuyer les parois intérieures de l'appareil de ventila- tion à l'aide d'un chiffon de nettoyage. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 13: Fonctions Spéciales

    T-air rejeté min. réglée à l'usine, l'appareil de ventila- d'installation du foyer baisse par rapport au tirage de la recte. En sélectionnant un préchauffage ou ré- 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 14: Commande Par Appli / Outil Web

    7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 15: Pièces De Rechange

    à 0157.1376.0000 Filtre secteur (Schurter) filtre leurs propriétaires ou leurs produits. CA FSS2-65-4/3 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 16: Schémas De Branchement / De Câblage

    AEREX website at www.aerex.de. The circuit diagrams can be found in the unit’s exhaust air area. 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 17: Fiches Techniques Du Produit

    Installation and operating instructions for geniovent.x 600 - 900 S Notice de montage et mode d'emploi geniovent.x 600 - 900 S Product data sheets / Fiches techniques du produit 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...
  • Page 18 Installation and operating instructions for geniovent.x 600 - 900 S Notice de montage et mode d'emploi geniovent.x 600 - 900 S 7185.1234.0003_RLF.9_02.23_AS Aerex HaustechnikSysteme GmbH I Steinkirchring 27 I 78056 Villingen-Schwenningen I Germany I Service +49 7720 694880 I info@aerex.de I www.aerex.de...

Ce manuel est également adapté pour:

Geniovent.x 900 s

Table des Matières