5. Commissioning, operation

Measuring range

The measuring range is set by installing jumpers on the corresponding
configuration elements J1 and J2.
EN
Measuring range 2 (0 ... 2 m/s)
J1
Jumper (J1): Installed
J2
Jumper (J2): Not installed
Measuring range 10 (0 ... 10 m/s)
J1
Jumper (J1): Not installed
J2
Jumper (J2): Installed
Measuring range 20 (0 ... 20 m/s)
J1
Jumper (J1): Installed
J2
Jumper (J2): Installed

Measuring mode

The desired output signal for both the temperature (T
(v
) outputs is selected by installing jumpers on the corresponding
out
configuration elements T and v. Both outputs must be configured
separately.
T
v
V
mA
T
v
V
mA
T
v
V
mA
T
v
V
mA
16
Temperature output (T
out
Air velocity output (v
out
Temperature output (T
out
Air velocity output (v
out
Temperature output (T
out
Air velocity output (v
out
Temperature output (T
out
Air velocity output (v
out
Jumper not
installed
)
T = voltage (V)
)
⇒ v = voltage (V)
)
T = current (mA)
)
⇒ v = current (mA)
)
T = voltage (V)
)
⇒ v = current (mA)
)
T = current (mA)
)
⇒ v = voltage (V)
WIKA operating instructions model A2G-20
Jumper
Jumper
installed
stored
) and air velocity
out

Publicité

Table des Matières
loading

Table des Matières