Installation / Maintenance - Pentair Hydromatic HCU Serie Notice D'utilisation

Pompes de récupération des eaux condensées
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation / Maintenance

Risk of Flooding. With installation
H.
No. 2 ("Safety Switch Sounds Alarm"), the alarm is
activated when the water level in the reservoir is
within about 1/2" of the top of the reservoir.
However, the furnace/AC unit will continue to
produce condensate because the alarm will not
shut it down. Monitor the installation so that in
case of high water level in the condensate reservoir
you can take action before the reservoir overflows
and flooding occurs.
Figure 2: Low Voltage Auxiliary Safety Switch connec-
tion for alarm circuit installation (does not shut down
furnace/AC unit).
testing auxiliary safety switch:
nOtICE: Some appliances may not start immediately due
to a built-in delay circuit that prevents rapid cycling of the
compressor.
1. Start appliance.
2. Unplug the condensate pump so that it cannot pump
out.
3. Pour water into the pump reservoir until it is almost
full.
4. As the water rises in the reservoir, the safety switch
should shut down the appliance or set off the alarm
(depending on the installation procedure used).
5. Plug in the condensate pump and allow it to empty
the reservoir. As the water level goes down in the
reservoir, the safety switch should reset, allowing the
appliance to start or shutting off the alarm.
MaIntEnanCE
1. Disconnect the power to the furnace/AC unit and
unplug the pump.
2. Disconnect the tubing to the pump. Drain the tubing
into a container.
3. Remove the two mounting screws and remove the
pump from the furnace or wall. Dump the reservoir
into a floor drain or container.
4. After you have dumped the pump, remove the four
screws securing the reservoir to the pump deck. Lift
the deck/pump assembly off of the reservoir.
5. Turn the deck/pump assembly upside down and
remove the five screws holding the impeller cover to
the motor.
6. Remove the impeller cover. The rotor/ impeller
assembly may come out with it. If not, pull it out of
the rotor chamber in the motor. (You may have to pull
it hard to get it out against the magnetism in the motor
windings.)
7. Clean the impeller, rotor, rotor cavity, and O-Ring.
Use a rag to clean the O-Ring groove in the impeller
cover and the sealing surface on the bottom of the
motor block.
8. Clean out the reservoir.
9. Reassemble the impeller and the impeller cover;
tighten the screws carefully. Do not overtighten!
10. Turn everything right side up and reassemble the
reservoir to the deck. Be sure the impeller cover fits
into the molded ring in the bottom of the reservoir.
Fasten the reservoir with the four screws at the
corners.
11. Reinstall the pump on the furnace.
12. Plug in the pump, fill the reservoir, and run the pump
through one complete pump-down cycle to be sure it
works correctly.
13. The pump is ready for operation.
CLEanIng thE ChECk VaLVE
1. Unplug the condensate pump.
2. Remove the discharge line from the check valve.
3. Use a 9/16" wrench to remove the check valve from
the pump deck.
4. Inspect the valve for obstructions or damage. Clean or
replace it as needed.
5. Thread the valve back into the pump discharge by
hand, plus 1/2 turn with the wrench.
nOtICE: Don't overtighten the valve, as
overtightening can distort the O-Ring that seals the
valve, causing leaks.
6. Plug in the pump, fill the reservoir, and run the pump
through one complete pump-down cycle to be sure it
works correctly.
7. The pump is ready for operation.
5

Publicité

Table des Matières
loading

Table des Matières