8
Table of content
Images
Installation
Installation of the built-in mounting frame into vertical shaft
Installation of the built-in mounting frame into vertical concrete shaft
Installation of the shutter in the built-in mounting frame
Installation
Installation of the built-in mounting frame into vertical shaft exc. concrete
1. Make an opening with dimensions (W+A) x (H+A) mm. A = 2 x thickness sleeve (e) + 20 mm.
Fit a sleeve of the same type and thickness of the duct (thickness e) of minimum 105mm deep for KAM, AVA
(ME) and 125mm deep for KAM MP in the opening.
See details per type of shaft in the product's installation guidelines.
2. Fasten and seal the mounting frame (see details per shaft type in the product's installation guidelines).
Two fastening plates are provided at the bottom and at the top of the mounting frame: fold these against the
sleeve.
In case of fixing by screws, fasten the mounting frame to the sleeve with chipboard screws (6 x e) mm. These
screws can be fixed in one of the openings provided for this purpose, depending on the depth of the sleeve.
Take care not to misshape the frame during its installation. The finished opening must be the same size as the
mounting frame (W+10) x (H+10) mm.
Installation of the built-in mounting frame into vertical concrete shaft
1. In case of screwing of the mounting frame:
Make an opening with dimensions (W+20) x (H+20) mm.
In case of sealing the mounting frame:
Make an opening with dimensions (W+20) x (H+20) till (W+100) x (H+100) mm.
2. The mounting frame should always be fastened to the concrete shaft with screws and dowels (Ø6 x minimum
60 mm, steel or stainless steel).
For an opening with dimensions up to (W+20) x (H+20) mm:
Two sealing lugs are provided at the bottom and at the top of the mounting frame: fold these against the shaft
and fasten the mounting frame to the lining with 4 screws Ø6 x 60 mm, taking care not to misshape it. These
screws can be inserted through any of the punched holes in the lugs, depending on the thickness of the shaft
wall. The finished opening must be the same size as the mounting frame (W+10) x (H+10) mm.
For an opening with dimensions up to (W+100) x (H+100) mm:
Apply mortar around the opening to reduce the opening to the outer dimensions of the frame, then proceed
as mentioned above to fasten the frame to the opening. Make sure that the gap between the frame and the
opening in sealed completely with mortar.
The mortar must harden completely before the damper is fastened to the mounting frame.
2
8
8
8
9
(Images A)
(Images B)

Publicité