Technical Data - Finder 7E.23 Instructions De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Assembly and operating instructions Type 7E.23
32 A 2-Ways Single Phase active power energy meter with Serial Modbus interface, Fig. 1
Description
Energy meter with serial Modbus interface (RS-485)
enables the reading of all relevant data like consump-
tion, current, voltage, power (active and reactive). The
reactive power (idle power) can only be read on the
Modbus interface.

Technical data

■ Fig. 2
Connection
diagram
■ Fig. 3
Dimensions
■ B according to EN50470-3,
Accuracy class
1 according to IEC62053-21
■ I
Reference, Maxi-
ref
mum, initial current
■ 230 V
operating voltage
Tolerance −20%/+15%
■ 00 000,00...999 999,9 kWh
Counting range
■ Integrated Modbus interface
Output
(see page with the telegram
structure)
■ Conductor cross-section max. 6 mm
Connections
Main circuit
screwdriver pozi no. 1, slot no. 1,
torque 1,2 Nm
■ Conductor cross-section max. 2,5 mm
Connections
Control circuit
screwdriver pozi no. 0, slot no. 1,
torque 0,5 Nm
■ −25... +55°C (noncondensing
Operating
temperature
according standard EN50470)
■ Mechanical M2
Environment
Electromagnetic E2
Indicating elements (Fig. 4)
■ Indicates the total consumption
T
(kWh)
■ Indicates the total feeding back
T
(kWh)
■ Indicates the instantaneous power
P (kW)
Current
Current
■ Indicates the voltage
U (V)
■ Indicates the current
I (A)
■ Pulsates according to the amount
2000 pulses/kWh
of used power.
32307734–001C
= 5 A, Im
= 32 A, Ist
20 mA
ax
=
, 50 Hz
AC
= consumption (pos.)
= feeding back (neg.)
Notes before connecting
In order to avoid moisture in the meter due to condensate
build-up, acclimatise the meter at room temperature for
about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk
of an electric shock.
Operation of the LCD display
See page with LCD menu navigation.
Installation instructions
The energy meter can be attached to a 35 mm rail
(EN60715TH35).
The meter can be used only in installation cabinets.
EC Declaration of Conformity
,
2
We,
,
2
Finder GmbH
Hans-Böckler-Strasse 44
DE-65468 Trebus-Astheim, Germany
declare under our sole responsibility that the products:
■ Active electricity meter
• Type: 7E.23.8.230.0204
• Type: 7E.23.8.230.0214
to which this declaration refers, conform to the require-
ments of the following directives:
■ 2014/32/EU
■ 2014/30/EU
■ 2014/35/EU in the respective valid version
and with the harmonised EN standards:
■ EN 50470-1:2006
■ EN 50470-3:2006
The following energy meters are approved for billing
to third parties
■ Active electricity meter:
• Type: 7E.23.8.230.0214
The notified body METAS-Cert, No. 1259 has tested
and certified conformity to type (Module D)
(www.metas.ch/certsearch).
Trebur-Astheim 10.01.2017
Signed
Manfred Cloot, Technical Manager
Finder GmbH
03.2017
English