Sunny Boy 2000
Quick Installation Guide
Sunny Boy 2000 Technical Data
Input voltage range V PV :
Max. input current I PVmax :
Nominal output power P ACnom :
Max. output power P ACmax :
To commission the Sunny Boy please make sure:
1. The Sunny Boy may only be commissioned by qualified
personnel.
2. Follow the order below when establishing the electrical
connection!
3. Check the open circuit voltage of the PV strings. Voltages
above 500 V can cause non-repairable damage!
4. Check the Sunny Boy for any transport damage.
5. Do not open the Sunny Boy when it is connected to the
grid.
Order for commissioning:
1. Disconnect the AC circuit the Sunny Boy is connected to
(open the circuit breaker in the AC house distribution).
2. Install the Sunny Boy (see page 2).
3. Check the PV open circuit voltage and the connection of
the PV strings.
125 V - 500 V
Output voltage range V AC :
10 A
Frequency range f AC :
1800 W
Weight:
2000 W
6. Never disconnect the Sunny Boy from the PV voltage be-
fore the AC voltage has been disconnected (remove the
fuse in the house distribution). Pulling the Multi-Contact
plug connectors while under load results in an electric
arc in the connector which consequently has to be re-
placed.
4. Assemble the AC plug (see page 3).
5. Connect the AC plug.
6. Connect the AC voltage
(close the house distribution circuit breaker).

Please read first

The following instructions for
installation will help you to
commission the Sunny Boy
2000. They do not replace
the Sunny Boy 2000 Manual.
You will find a complete des-
cription of all functions as
well
as
information
communication equipment
and all definable parameters
in the Sunny Boy 2000
Technical Description.
198 V - 251 V
49.8 - 50.2 Hz
approx. 25 kg