6. Operating test:
- Following installation, an operating test should be conducted with each connected
sensor.
6.1 Switch on the G.A.S.-pro and wait until the warm-up phase has been completed,
and the power indicator flashes.
6.2 Now allow cigarette lighter gas to flow onto Sensor 1. After a few seconds the
alarm sounds.
6.3 Wait approx. 30 seconds and repeat the process with all connected sensors.
The CO-Sensor does not have to be tested. Test of the CO-Sensor can not be carried
out with lighter gas but only with carbon monoxide.
7. Troubleshooting:
- If the operating test does not trigger an alarm, check the wiring using the terminal
diagram.
- If, after initial switch-on and the end of the warm-up phase, an alarm sounds
immediately, the sensor may not have been stored properly, and is therefore
heavily soiled. Repeat the switch-on procedure several times until the alarm no
longer sounds.
- If a problem other than the one described occurs, please check the wiring using the
terminal diagram. If the fault is not in the wiring, please contact your dealer or our
technical hotline.
Technical specifications:
Power supply:
Current consumption: approx. 10 mA (central unit)
Weight:
Detection:
Delivery scope:
36 month warranty from date of purchase.
To prevent damage to the device, use only genuine Thitronik accessories.
Otherwise the warranty will be voided!
Compatible accessories:
External siren
Additional sensor
CO sensor
External LED
Back up siren
9-30 VDC
approx. 75 mA (per sensor)
approx. 40 mA (CO sensor)
approx. 140 g
from 50 ppm narcotic gas, propane, butane
from 300 ppm carbon monoxide (optional)
Central unit incl. sensor, alarm sticker, manual
and mounting materials.
Art. No.: 100191
Art. No.: 100456
Art. No.: 100433
Art. No.: 100034
Art. No.: 100089
7