Electrical Wiring Connection - McQuay J Serie Manuel D'installation

Masquer les pouces Voir aussi pour J Serie:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 59
IMPORTANT :*
The figures shown in the table are for information purpose only. They should be checked and
selected to comply with the local/national codes of regulations. This is also subject to the type of
installation and conductors used.
**
The appropriate voltage range should be checked with label data on the unit.
Indoor Unit
Terminal Block
1
2
SIG
N
L
• All wires must be firmly connected.
• All wires must not touch the refrigerant piping
compressor or any moving parts of the fan motor.
• The connecting wires between the indoor unit and the
outdoor unit must be clamped on the wire clamps.
• The power supply cord must be equivalent to H07RN-
F(245IEC57) which is the minimum requirement.
Acson IM-WMJ-0109(0).indd 9
All manuals and user guides at all-guides.com

ELECTRICAL WIRING CONNECTION

Outdoor Unit
Terminal Block
1
2
SIG
Power Supply
Cable
There must be a double pole switch with
a minimum 3mm contact gap and fuse/
circuit breaker as recommended in the fixed
installation circuit.
1-9
Model
Voltage range
Power supply cable size*
mm²
Number of core
Interconnection cable size
mm²
Number of core
Recommended time delay fuse
A
* If the length of the cable is more than 2m, use cable
with bigger size.
10/15
220V - 240V / 1Ph / 50Hz+
1.5
3
1.5
4
15
2009-4-8 9:10:13