HPZC10*
Boiler Controls
Resideo Hydronic Panels are capable of managing boilers with DHW priority. The panel features two isolated end
switches labeled Boiler and End Switch for TT outputs to the boiler. Two slide switches are available to provide simple
programing of the end switches to meet the desired application. See the operational matrix below detailing functionality
of the switches.
Additionally, this panel features an end switch for every zone valve, one of which must be closed for pumps and boiler to
be activated.
WAIT FOR
PRIORITY ZONE
TO SATISFY
T-STAT
CALL
WAIT FOR
PRIORITY ZONE
TO SATISFY
33-00360EF—08
NO PRIORITY ZONE OR PRIORITY END SWITCH
VALVE
T-STAT
POWERED
CALL
PRIORITY ZONE, NO PRIORITY END SWITCH
DEACTIVATE ALL
OTHER ZONES
YES
IS THIS THE
T-STAT
PRIORITY ZONE?
CALL
NO
IS PRIORITY
ACTIVE?
YES
NO
PRIORITY ZONE, PRIORITY END SWITCH
DEACTIVATE ALL
OTHER ZONES
YES
IS THIS THE
PRIORITY ZONE?
NO
IS PRIORITY
ACTIVE?
YES
NO
CLOSED
STATUS OF
VALVE END
SWITCH
OPEN
Fig. 13.
VALVE
STATUS OF VALVE
POWERED
END SWITCH
Fig. 14.
CLOSED
VALVE
STATUS OF VALVE
POWERED
END SWITCH
OPEN
CLOSED
VALVE
STATUS OF VALVE
POWERED
END SWITCH
OPEN
Fig. 15.
6
BOILER RELAY = ON
END SWITCH = ON
BOILER RELAY = OFF
END SWITCH = OFF
M37147
CLOSED
BOILER RELAY = ON
END SWITCH = ON
BOILER RELAY = OFF
END SWITCH = OFF
OPEN
M37148
BOILER RELAY = ON
END SWITCH = ON
BOILER RELAY = OFF
END SWITCH = OFF
BOILER RELAY = ON
END SWITCH = OFF
BOILER RELAY = OFF
END SWITCH = OFF
M37149