Replacing the Batteries
Use only 3V lithium batteries listed on the battery compartment cover.
1. To remove the unit from the mounting base, grasp the unit and turn
it counterclockwise approximately 15 degrees.
2. Slide the battery compartment cover away from the alarm to unsnap
it and lift it off. See Figure 2.
3. Remove the batteries and dispose of them properly.
4. Observing correct polarity, insert two new 3V lithium batteries into
the battery compartment and replace the cover.
5. Reattach the unit to the mounting base. See Installation, Step 5.
6. Test the system.
Cleaning
Clean the cover with a dry or damp (water) cloth as needed to keep it
free from dust and dirt.
When necessary, clean the interior and replace the optical chamber
(part #211) as follows:
1. To remove the unit from the mounting base, grasp the unit and turn
it counterclockwise approximately 15 degrees.
2. Remove the batteries.
3. Slide a flat-blade screwdriver in the slot on the alarm cap and gently
push the handle down to pry the alarm cap up and off. See Figure 4.
4. Squeeze the optical chamber where indicated and pull it up and away
from the optical base and discard. See Figure 5.
5. Blow out or use a soft-bristled brush to remove all dust and dirt from
the optical base.
6. Line the new optical chamber up with the optical base by lining up
the the arrows on the optical chamber to the latches on the optical
base. Ensure that the LED cavity in the optical chamber is above the
LED and snap the optical chamber down into place.
7. Replace the alarm cap as follows:
-Line the alarm cap up with the unit.
-Insert the alarm cap into the unit and turn clockwise approximately
15 degrees. It should snap firmly into place.
8. Observing the proper polarity, replace the batteries and the battery
compartment cover.
9. Reattach the unit to its mounting base. See Installation, Step 5.
10. Test the unit sensitivity.
Maintenance
The units are designed for easy field service and maintenance. When
installed and used properly, they require minimal maintenance.
The units should be tested weekly.
When a unit listed with a transmitter requires maintenance, it extin-
guishes its LED and initiates the external signals described in the
following table.
S i g n a l
Action Required
CleanMe
Sensitivity is out of range and the unit needs
cleaning. See Cleaning.
Maintenance Alert Unit failed to power up on self test. Perform a
sensitivity test. See Sensitivity Test. If the problem
persists, replace the unit.
Low Battery
Batteries in the unit are low. Replace the batteries.
ESL 560N Series
Specifications
Voltage
Typical average standby current
Typical test current
Typical alarm current
Battery type
Low battery threshold
Sounder
Low battery beep rate
Sensitivity
Operating temperature
Operating humidity range
Color
Alarm dimensions
Base dimensions
Drift compensation adjustment
Heat detector specifications (T models):
Rate-of-rise
Fixed
Listings
FCC Compliance
This device complies with Part 15 of the FCC rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference. (2) This device must accept any interference received,
including interference that may cause undesired operation.
Means of Conformity
We declare under our sole responsibility that this product is in confor-
mity with Directive 93/68/EEC (Marking) and Directive 89/336/EEC
(EMC) based on test results using (non)-harmonized standards in
accordance with the Directives mentioned.
Product Ordering
Model
Description
560NS
3V standalone smoke alarm, 85dBa sounder UL 217
(OEM customers call for transmitter compatibility)
562NS
3V standalone smoke alarm, two 3V lithium batteries,
85dBa sounder UL 217 (OEM customers call for
transmitter compatibility)
562NST
3V standalone smoke alarm, two 3V lithium batteries,
85dBa sounder, 135°F fixed/rate-of-rise heat detector, UL
217 (OEM customers call for transmitter compatibility)
Accessories
SM-200
Smoke! in a can® (canned smoke) for functional testing of
smoke alarms
SMEXT-1
Extension tube for Smoke! in a can®
211
Field replaceable optical chambers (set of 10)
60-933
6 pack 3V lithium button top batteries
Certain items in the installation instructions are protected under one or
more of the following patents: 5,546,074; 5,798,701; 5,821,666;
6,756,906
3VDC
35µA
2mA
70mA
®
3V lithium, Duracell
123,
®
®
Panasonic
CR123A, Sanyo
123A
2.70V causes low battery signal
85dBa at 10' temporal pattern
1 every 45 sec.
2.2% ± 1.3% / ft.
40°-100°F (4.4°-37.8°C)
0-95% non-condensing
White
5.6" x 2.4" (14.2cm x 6.1cm)
5.4" x 0.46" (13.7cm x 1.17cm)
0.5% / ft. max.
15°F/min>105°F (8.3°C/min>
40.6°C)
135°F ± 5°F (57.2°C ± 2.8°C)
UL217, CE, C-UL US, CSFM