Maintenance
Monitor the cleanliness, level of the neutralization media, and pH level in the capsule monthly. Remove any precipitate
coating or debris found to prevent blockages. Check the pH level at the outlet of the neutralizing kit using a suitable pH test
strip paper or an electronic pH meter for precise measurement. The neutralizing media should be replaced when the pH level
drops below the minimum level of the local water authority, when the float rises (see figure 4 below), or after one year,
whichever comes first. For replacement LipHter+ media contact your local Axiom distributor.
Normal Operation
Float is
down
The float should be down during normal operation. If flow in the NC-1W becomes restricted, the float will rise and lock in
position, indicating that the media should be cleaned or replaced (see figure 4 above). After replacing the media, reset the float
by pushing it back down.
ATTENTION: ADDITIONAL MAINTENANCE FOR BOILERS WITH ALUMINUM HEAT EXCHANGERS
-
Boilers with Aluminum heat exchangers deposite white salt on the neutralization media that restricts flow
through the neutralizer. To clean the media, remove the clear jar, rinse the media with water, and twist the jar
back onto the lid.
Figure 5: Salt precipitate deposited on neutralization
media from Aluminum heat exchangers
Limited Warranty
The unit is warranted against defects in materials and workmanship for one year.
Patent Pending
Figure 4
Figure 6: Neutralization media that has been
rinsed with clean water
Restricted Flow
Float is up, and
locked in position,
indicating the
neutralizer requires
cleaning or
replacement media.