Fig. 6 - Modbus register
Address:
Slave ID: 0x70 – 0x7F (depending on encoder setting)
Coil Stat Bits:
0x01: Read
0x05: Write Single Coil (NOTE: ON => output value = 0xFF00)
0x0F: Write Multiple Coils
Register
Address
Function
1
0
Relay 1
2
1
Relay 2
3
2
LED 1 (green)
4
3
LED 2 (red)
Input Stat Bits:
0x02: Read
Register
Address
Function
1
0
DigiIn1 state
2
1
DigiIn2 state
3
2
Sensor 1 Alarm
4
3
Sensor 2 Alarm
Holding Registers:
0x03: Read
0x06: Write Single
0x10: Write Multiple
Register
Address
Function
1
0x0000
0 - 10V Out 1
2
0x0001
0 - 10V Out 2
Input Registers:
0x04: Read
Register
Address
Function
1
0x0000
SW Version
2
0x0001
Analog In 1
3
0x0002
Analog In 2
4
0x0003
Sensor 1
5
0x0004
Sensor 2
^
Stenager 13B • DK-6400 Sønderborg
Tél. : +45 73 12 13 14 • Fax +45 73 12 13 13
oj@ojelectronics.com • www.ojelectronics.com
The trademark is a registered trademark belonging to OJ Electronics A/S · © 2018 OJ Electronics A/S
Range
Resolution
0 – 1
1 = on
0 – 1
1 = on
0 – 1
1 = on *
0 – 1
1 = on *
Range
Resolution
0 – 1
1 = Hi
0 – 1
1 = Hi
0 – 1
1 = alarm
0 – 1
1 = alarm
Range
Resolution
0 – 10000
0.001
0 – 10000
0.001
Range
Resolution
0 - 65535
0.01
0 - 1000
0.01
0 - 1000
0.01
-4000 - 10000
0.01
-4000 - 10000
0.01
^
K
OJ ELECTRONICS A/S
Unit
-
-
-
-
Unit
-
-
-
-
Unit
V
V
Unit
-
V
V
ºC
ºC