Table 46-1 Modbus Variable Lists
data type
bit
bit
16 bit
16bit
HUMIDICLEAN HC 6000 protocoles communication
attribute
data address
10001 Fill valve status 0:off 1:on
10002 Drain valve status 0:off 1:on
10003 contactor 1 status 0:off 1:on
read only
10004 contactor 2 status 0:off 1:on
10005 contactor 3 status 0:off 1:on
10006 contactor 4 status 0:off 1:on
10008 Network control
1 comm type
2 Sensor select 0:Humidistat 1:RH sensor
3 High limit sensor select 0:not use 1:use
read write
4 Outside temperature 0:not use 1:use
5 Network enable 0:disable 1:enable
6 Modulating Fill enable
30001 Desired RH
30002 Output
30003 Water level
Run status
30004
5:Failure 6:Drain 7:heat 9:Fill
30005 Bed life (Hours)
30006 Bed life (Minutes)
30007 Run Time (Hours)
30008 Run Time (Minutes)
30009 Drain Freq (Hours)
30010 Drain Freq (Minutes)
30011 Idle Time (Hours)
30012 Idle Time (Minutes)
read only
30013 RH value
30014 Duct value
30015 Outside temperature
30016 Water temperature
30017 Heat temperature
Failure 1:Over temperature 2:High humidity/sail switch circuit is
open 3:Illegal level switch state 4:Unit have reached 100% of
bed life 5:Fill time out to low level 6:Water level dropped below
30018
level during normal run 7:Fill time out from low to high level
8:Water level above high level time out 9:Water level has not
dropped below low level during an emptydrain 10:End of bed
dring
30019 Contactor number
30020 Contactor Power 0:1000W 1:3000 2:5000W 3:6650W 4:8000W
40001 Language Select
40002 Set RH(Set Desired RH)
40003 High set point
40004 Outside temperature high set point
40005 Outside temperature low set point
40006 Outside RH low set point
40007 Run mode 1:Steam Gen 2:Manual Fill 3:Manual Drain 4:Unit stop
40008 AQUASTAT
Bed life 0:500Hours 1:750Hours 2:1000Hours 3:1250Hours
40009
4:1500Hours 5:1750Hours 6:2000Hours 7:2250Hours
8:2500Hours 9:3000Hours 10:No bed
Drain Freq 0:6Hours 1:12Hours 2:24Hours 3:48Hours
40010
4:96Hours
40011 Drain time 0:1Minutes 1:5Minutes 2:10Minutes
read write
40012 Signal type 0:0-10V 1:0-5V 2:1.9-3.9V 3:4-20mA
40013 PID_DIV
40014 PID_PB
40015 PID_SI
40016 PID_DG
40017 Modulating Fill Freq
40018 Modulating Fill time
40019 Water temperature compensate
40020 Heat temperature compensate
40021 First run
40022 Idle time
40023 Drain time 0:1Minutes 1:5Minutes 2:10Minutes
40024 Bed life
devatec
Distribué par :
Téléphone : 33 (0) 2 35 04 61 41—Télécopie : 33 (0) 2 35 61 62
www.devatec.com—france@devatec.com—export@devatec.com
tables des adresses
description
0:Local 1:Remote
0:485 1:PSP
0:enable 1:disable
0:low 1:normal 2:high 3:exception
0:Idle 1:Gen 10:frequent Draining 4:bed dring
87 rue du Feu Saint ELOI 76550 AMBRUMESNIL
47
For modbus function number
function 2 , read only MODBUS POLL:
READ DISCRETE INPUT
function 1,read only : function 5,15 write
MODBUS POLL: READ COILS
function4 , read only MODBUS POLL:
READ INPUT REGISTERS
function3 read only,function 6,16 write
MODBUS POLL: READ HOLDING
REGISTERS
function 6 , for debug only