2. Installation of the unit

2.1. Suspension

The wall suspension bar supplied with the unit is fixed to the wall and the dehumidifier is hung up on it. It
is important to mount the unit in a horizontal position to secure correct outflow of the condensate water.
To make sure that the room air passes unimpededly through the dehumidifier, air inlet and air outlet
openings must be free.
It is important that the dehumidifier is not installed near a source of heat as for example a radiator, and
doors and windows must be kept closed when the dehumidifier is in function.
NOTE! Dantherm recommends a minimum
distance between dehumidifier and
ceiling and dehumidifier and floor of
225 mm.
*The dimensions indicate the placing

2.2. Condensate outlet

The condensate outlet is located at the bottom of the dehumidifier. The unit has a drain spigot intended
for connection of a ½'' flexible or fixed water connection. If water drain through the wall is chosen, a
suitable hole is made in the wall and the condensate hose is led out through this hole, before suspending
the dehumidifier on the wall suspension bar.
It is important that the hose from the dehumidifier to the drainage has a fall of at least 2% to make sure
that the water runs away from the condensate tray.
As an alternative a condensate pump can be fitted at the water outlet to pump the water to a drain.
The placing of the condensate outlet is shown on the drawing below – the unit is seen from above.