Operating Instructions
Transducer for AC voltage SINEAX U 553
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
Contents
1. Read first and then ... ................................................. 9
2. Brief description ......................................................... 9
3. Technical data ............................................................ 9
4. Mounting ................................................................... 10
5. Electrical connections ............................................... 10
7. Commissioning and maintenance ............................ 11
8. Releasing the transducer .......................................... 11
9. Instruments admissions ............................................ 11
10. Dimensional drawing ................................................ 12
1. Read first and then ...
The proper and safe operation of the device
assumes that the Operating Instructions is
read carefully and the safety warnings given
in the various Sections
4. Mounting
5. Electrical connections
6. Adjustable measuring range
by DC calibration
are observed.
The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.

2. Brief description

The SINEAX U 553 measuring transducer is used to convert
a sine-wave or distorted AC voltage.
The output signal, in the form of a load independent DC
current or voltage, is proportional to the measured value.

3. Technical data

Measuring input
Nominal frequency:
50/60 or 400 Hz
Nominal input
voltage:
0 - 20 to 0 - 690 V
All manuals and user guides at all-guides.com
Measuring output
DC current:
0(0.2) - 1 to 0(4) - 20 mA
Burden voltage:
15 V
max. [kΩ] ≤
External resistance:
R
ext
I
= Full output value
AN
DC voltage:
0(0.2) - 1 to 0(2) - 10 V
[kΩ] min. ≥
External resistance:
R
ext
Response time:
50 or 300 ms
Power supply
AC/DC power pack (DC or 40 - 400 Hz)
Rated voltage
85 - 230 V DC / AC
24 - 60 V DC / AC
≤ 1.5 W resp. ≤ 3 VA
Power consumption:
Options
Connected to the low
tension terminal side:
24 V AC or 24 - 60 V DC, see Fig. 3
Power supply from
measuring input
≥ 24 - 60 V AC or 85 - 230 V AC,
(self powered):
see Fig. 4
Please note the max. and min. measuring input voltage!
Type label
Input voltage
inscription
range
= internal power
supply range
Self powered
by 1/2
24 - 60 V AC
(int. 24-60 V)
Self powered
by 1/2
85 - 230 V AC
(int. 85-230 V)
Accuracy (acc. to IEC 688)
Reference value:
Output end value
Basic accuracy:
Class 0.5
Safety
Pollution degree:
2
Installation category:
III
Environmental conditions
Operating temperature: - 10 to + 55 °C
- 40 to + 70 °C
Storage temperature:
Relative humidity of
≤ 75%
annual mean:
15 V
I
[mA]
AN
U
[V]
A
2 mA
Tolerance
DC - 15 to + 33%
AC ± 15%
Tolerance Power
supply
connec-
tion
Internal
± 15%
measuring
input
9