MVS
VARIATEUR ÉLECTRONIQUE,
RAIL DIN
HOLDING REGISTERS
Data type
Device slave
1
unsigned int. Modbus device address
address
Modbus baud
2
unsigned int. Modbus communication baud rate
rate
3
Modbus parity
unsigned int. Parity check mode
4
Device type
unsigned int. Device type (Read only)
5
HW version
unsigned int. Hardware version of the device (Read only)
6
FW version
unsigned int. Firmware version of the device (Read only)
7
Operating mode unsigned int.
8
Output override
unsigned int.
9-10
Analogue input
11
unsigned int.
type
Ascending /
descending
12
unsigned int.
analogue input
mode
Maximum
13
unsigned int.
output voltage
Minimum output
14
unsigned int.
voltage
15
Enable off level
unsigned int.
16
Off level value
unsigned int.
Kick start / soft
17
unsigned int.
start
Kick start / soft
18
unsigned int.
start duration
Remote control
19
unsigned int.
functionality
Analogue input
20
unsigned int.
functionality
21
Operation timer
unsigned int.
22-30
Output override
31
unsigned int.
value
32-40
Pour en savoir plus à propos de Modbus sur liaison série, s'il vous plaît visitez:
MIW-MVS-FR-002 - 02 / 05 / 18
Description
Enables Modbus control and disables the DIP switch and
trimmers
Enables the direct control over the output. Always
settable. Active only if holding register 7 is set to 1.
Reserved, returns 0
Selects the analogue input type of the device. Always
settable. Active only if holding register 7 is set to 1.
Ascending / descending analogue input mode. Depends on
the selected analogue input type. Always settable. Active
only if holding register 7 is set to 1.
Maximum settable output voltage. Always settable.
Active only if holding register 7 is set to 1.
Minimum settable output voltage. Always settable. Active
only if holding register 7 is set to 1.
Enables off level. Always settable. Active only if holding
register 7 is set to 1.
Off level value. Depends on the selected analogue input
type and ascending  /  descending analogue input mode.
Always settable. Active only if holding register 7 is set to 1.
Selects kick start or soft start. Always settable. Active
only if holding register 7 is set to 1.
Sets the duration time. Always settable. Active only if
holding register 7 is set to 1.
Sets the remote control input mode. Depends on the
selected kick start or soft start mode. Always settable.
Active only if holding register 7 is set to 1.
Sets the analogue input functionality. Depends on the
selected kick start or soft start. Always settable. Active
only if holding register 7 is set to 1.
Sets the operation time of the device when Timer mode by
remote control input or Logic mode by the analogue input
is selected. The operation time is additional to the kick
start / soft start duration times. Always settable. Active
only if holding registers 7 and 19 or / and 20 are set to 1.
Reserved, returns 0
Override value for the analogue output. Always settable.
Active only if holding register 8 is set to 1.
Reserved, returns 0
www.sentera.eu
Retour à la Table des matières
Data
1—247
MVSX-DM =
XXXX
XXXX
75—100
30—70
0—40
60—100
0—60
0—200
30—100
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
Default
Values
1
1 =
2 =
1—4
2
3 =
4 =
0 =
0—2
1
1 =
2 =
3009
0 x 0300
HW version
=
0 x 0140
FW version
=
Standalone
0 =
0—1
0
1 =
0 =
0—1
0
1 =
0 =
0—20 mA
0—1
1
1 =
0—10 VDC
0 =
10—0 VDC
1 =
0—10 VDC
0—1
1
0 =
20—0 mA
1 =
0—20 mA
75 =
100
100 =
100 % Us
30 =
30
70 =
0 =
0—1
0
1 =
Ascending mode:
0 =
40 =
0 =
40 =
0
Descending mode:
100 =
10,0 VDC
60 =
100 =
60 =
0 =
Soft start
0—1
1
1 =
Kick start
0 =
10
60 =
0 =
Normal mode
0—1
0
1 =
Timer mode
0 =
0—1
0
1 =
Logic mode
0 =
60
200 =
0 =
0,
0
30 =
100 =
100 % Us
9.600
19.200
38.400
57.600
8N1
8E1
8O1
3.00
1.40
mode
Modbus
mode
Disabled
Enabled
or
75 % Us
30 % Us
70 % Us
Disabled
Enabled
Voltage
0 VDC
4,0 VDC
Current
0 mA
8,0 mA
Voltage
6,0 VDC
Current
20,0 mA
12,0 mA
0 s
60 s
Normal
mode
0 s
200 s
0 % Us
30 % Us
13 - 17