Operating range
The JRGURED Combi domestic water station is
authorised for the following operating ranges:
JRG Nr. 1350/1353 PN 16
Water temperature:
Primary pressure:
Secondary pressure (adjustable): 2– 6 bar*
JRG Nr. 1360/1363 PN 25
Water temperature:
Primary pressure:
Secondary pressure (adjustable): 2– 6 bar*
* Other pressure settings to order.
** With filter tube JRG Code 1839 max. 70ºC.
Identification
– 1, 1¼, 1½, 2 (DN/valve size)
– JRGURED Combi (name of fitting)
– JRG (manufacturer)
– Flow direction arrow
Factory setting
The JRGURED Combi domestic water sta tion is
factory -set to a secondary pressure of 4 bar.
Commissioning
max. 30ºC
max. 16 bar
max. 30ºC**
max. 25 bar
The water station is in operation.
Resetting the pressure -reducing valve
Before putting the JRGURED Combi
domestic water station into operation,
thoroughly flush the infeed pipe.
Slowly open the stopcock 15 upstream
from the water station.
Any change to the factory pressu re
setting is carried out exclusively
on the responsibility of the person
doing so.