Honeywell Home HM750A1000 Instructions D'installation page 6

Humidificateur à vapeur à électrodes évolué
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

HM750A1000
LOCATION
Mount on a suitable wall or vertical surface. Do not sit the
unit on the floor. Allow clearances required for plumbing
and electrical connections. Clearance dimensions shown
are for reference only and are the minimum required for
maintenance of the humidifier.
41˚ - 104˚ F
4 INCHES (102 MM)
(5˚ - 40˚ C)
0-95%
NON CONDENSING
1
24 INCHES (610 MM)
1
1 INCH (25 MM) IF WIRED BEFORE MOUNTING.
36 INCHES (914 MM) FOR WIRING ACCESSIBILITY.
Fig. 3. Clearances for the HM750.
Consult local and national codes before final location and
installation. Resideo does not accept responsibility for
installation code violations.
• Install only in areas with ambient temperature 41 to
104 °F (5 to 40 °C) and relative humidity 5 to 95 %,
non-condensing.
• Humidifier must be installed below the steam
distributor nozzle. Take care to provide proper steam
line routing.
• DO NOT locate the humidifier any further than
absolutely necessary from the steam distributor nozzle
location as net output will be reduced as a result of heat
loss through the steam line.
• When possible, mount the HM750 humidifier at a
height convenient for servicing.
NOTE:
Do not mount on surfaces above 176 °F (80 °C),
where freezing can occur, vibrating surface, or floor.
Fig. 4. Distributor nozzle installed vertically
in a horizontal duct. (Remote mount)
33-00289EF—05
1 INCH
(25 MM)
M36860A
1/2 DUCT WIDTH
M37234
Steam Nozzle Location
Whether the humidifier is being installed directly on the
air duct or remotely, the location of the distributor nozzle
in the air duct should follow the subsequent rules:
4.5 (114)
AIR FLOW
Fig. 5. Distributor installed horizontally (side mount)
in a horizontal duct. (Remote mount)
Measurements in inches (mm).
1/2 DUCT
WIDTH
Fig. 6. Distributor nozzle installed horizontally
in a vertical duct. (Remote mount)
6
1
8 (204)
MINIMUM
1
MINIMUM CLEARANCE TO TOP OF DUCT.
AIR FLOW
M37233
M37232