Function Check - Siemens REV24 Série Instructions D'installation

Masquer les pouces Voir aussi pour REV24 Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 8
1.1.7 Heating or cooling mode: DIP switch 9
DIP switch 9 ON:
Cooling mode
DIP switch 9 OFF:
Heating mode (factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.8 Radio clock: DIP switch 10
Can only be used with REV..DC (with integrated DCF77 receiver for
time signal from Frankfurt)!
DIP switch ON:
Clock runs on built-in
2
Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
seconds, press simultaneously
access the expert level for making the settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
settings by pressing
.
The expert level is quit by pressing the operating mode selection button
Code list
Function block
Code
00
Basic settings
01
02
10
LCD settings
11
12
30
Clock settings
31
32
Note 1:
If the radio clock is not active or not present, this setting has no impact.
With the radio clock active, the time signal received from Frankfurt is shifted by the value set under code 30 (time zone).
Note 2:
If the radio clock is not active or not present, the time change always takes place at 02:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
Note 3:
If the radio clock is not active or not present, the time change always takes place at 03:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
3

Function check

a) Check the display. If there is no display, check the batteries
b) "Continuously Comfort mode"
c) REV.. in heating mode: Set the temperature setpoint to a level
above the displayed room temperature (see operating instructions)
REV.. in cooling mode: Set the temperature setpoint to a level below
the displayed room temperature (see operating instructions)
d) The relay and thus the actuating device must respond within
1 minute. Symbol
appears on the display. If not:
Check actuating device and wiring
In heating mode, the room temperature is possibly higher than
the adjusted temperature setpoint, in cooling mode possibly
lower
e) Set temperature setpoint of "Continuously Comfort mode"
required level
f)
Select the required operating mode
CE1G2205xx
quartz
and
for 3 seconds, release
Name
Language
Sensor calibration
Switching differential 2-point
Illumination time
Background brightness
Contrast
Time zone
Deviation from time signal received from
Frankfurt (Central European Time CET)
(refer to Note 1)
Start of summer time (refer to Note 2)
End of summer time (refer to Note 3)
, read the temperature displayed
DIP switch OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.9 DIP switch reset (Fig. )
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
and
for 3 seconds, then release the buttons and, within 3
and keep
depressed for another 3 seconds. This enables you to
on display (also refer to Fig. G).
.
Factory setting
English
off
0.5 °C
10 seconds
0
0
0 hours
March 31 (31-03)
October 31 (31-10)
4
Reset
User-defined settings:
Press simultaneously
All temperature and time settings of the slider positions are reset to
their default values (refer to section "Factory settings" in the
operating instructions). The settings made on the expert level will
remain unchanged.
The clock starts at 12:00, the date on 01-01-08
(01 - January - 2008). During the reset time, all sectors of the
display are illuminated and can thus be checked.
All user-defined settings plus those made on the expert level:
Press simultaneously the DIP switch reset button,
5 seconds:
After this reset, all factory settings will be reloaded. This applies to
both the slider settings and the settings made on the expert level.
to the
Notes
The controller is classified as a device of software class A and
designed for use in environments with normal degree of
pollution
18.02.2008
Time signal DCF77 from Frankfurt
).
)
and
Your setting
,
and
for 3 seconds:
. Confirm the
and
for
7/44

Hide quick links:

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Rev13 série