Télécharger Imprimer la page

D+H NSV 401 Notice Originale page 7

Publicité

Les langues disponibles

Les langues disponibles

Content
Safety notes / Scope of supply / Technical data / Proper use / Features / Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System description / Schematic design / NM 650 emergency power supply module connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GM 650 group module connection / Power supply connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
NSV 401 overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Connection / Replacement of batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety notes
Operating voltage 230 VAC!
Risk of injury from electric shock!
The mains supply must be in-phase!
The NSV 401 may not, under any circumstances, be operated without
an earthed conductor!
- The output limits of the apparent and effective output may not
be exceeded
- Observe the safety notes when changing/assembling the battery (see page 11)
- Only an authorised electrician may connect and work on the NSV 401
- In case of surface condensation, at least 2 hours are required for
acclimatisation
- Do not install the NSV 401 near heat sources; unrestricted air circulation
must always be ensured
Commissioning
Proper connection of the 230 V AC cables and battery connections (see
page 11) must be verified prior to commissioning.
Scope of supply
Emergency power supply with battery cover/fuse and NM 650.
Batteries must be ordered separately.
Technical data
Type
Mains input:
Input range
Nominal frequency
Overvoltage control
Undervoltage control
Nominal power
NSV output:
Max. connection load 18 Ah Battery
Max. connection load 12 Ah Battery
Mains operation
Back-up operation
Max. output current
Overload capacity
Efficiency:
Battery connection:
Nominal voltage
Environmental data:
Permissible temperature range
Recommended temperature
General:
Cooling
Noise level
Dimensions
Battery:
Max. battery dimensions
Battery capacity 18 Ah
Battery capacity 12 Ah
99.824.04 1.4/06/21
NSV 401
230 V AC, -10% / +15%
50 Hz
yes (-13%)
yes (+13%)
max. 3200 VA / 2000 W (14,6 A)
3200 VA / 2000 W
1600 VA / 1000 W
197 - 250 V AC
230 V AC (Sinus +/- 5%)
13,9 A
[110 ... 130 %]: 10-25s, > 130% 1,5s
AC -> AC
> 95%
48 V DC (nominal)
-5 ... +40°C
+15 ... +25°C
Fan cooling
< 45 dB
355 x 250 x 205 mm (W x H xD)
181 x 167 x 76 mm (W x H xD)
4 x Art.-Nr. 70.200.05 Type 5
(Construction identical to
"Long WP18-12")
4 x Art.-Nr. 70.200.00 Type 4
(Construction identical to
"Long WP12-12")
English
Intended use
Emergency power supply for 230 VAC SHEV systems in the event of an
alarm. In connection with RZN 43xx-E control panels and 230 VAC SHEV
group plug-in cards GE 650 and the NM 650 emergency power supply
module.
Features
- True sinusoidal voltage at the output of the NSV 401, marginal
distortion factor
- The parallel circuit of several NSV 401 is prohibited
- 230 VAC emergency power supply
- 72 hr. standby without power supply
System description
The NSV 401 is an emergency power supply for 230 VAC D+H SHEV
systems. In combination with the GE 650 set, the NSV 401 supplies the
connected SHEV drives with mains voltage. In case of power failure they
are supplied with 230 VAC for 3 minutes (72 hr. standby) by the system's
battery bank . Any ventilation units connected to the system may not be
supplied by the NSV 401.
Typ 4
ca.100 mm
ca.151 mm
ca.99 mm
ca.167 mm
Typ 5
ca.181 mm
ca.76 mm
7/24
NSV 401

Publicité

loading

Produits Connexes pour D+H NSV 401