Start-Up Sequence; Settings - Tecumseh INFINEE Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.

Start-up sequence

Settings

Before starting the unit, set the following parameters:
Enter the glycol level of the installation
Set the temperature setpoint on the water return
Adjust the temperature difference between the water return and the water outlet
Enter the compressor start and stop thresholds around the setpoint value
Enter the compressor operating frequencies
Enter the desired output type for alarm return and compressor operation
It is advisable to change the USER password, by default the password = 0000
Fill in the settings table.
These parameters can be modified and are accessible in the Setpoints menu
Designation
Percentage of glycol in the installation
Temperature setpoint on the water return
Temperature setpoint on the delta between
water return and water outlet
Offset on compressor start-up setpoint
Offset on setpoint at compressor stop
Minimum compressor frequency
Maximum compressor frequency
Compressor frequency in ECO mode
USER password
Enable unit start-up
Version: 2020-01
Control User Manual
Default
value
33%
10.0°C
5.0°C
1.5°C
1.5°C
25 Hz
85 Hz
50 Hz
0000
TECUMSEH EUROPE S&L
2 av. Blaise Pascal, 38090 Vaulx Milieu
Tel. : +33 (0)4 74 82 24 00 - www.tecumseh.com
INFINEE chillers
Minimum
Maximum
value
value
25%
50%
-10.0°C
25.0°C
0.0°C
20.0°C
0.5°C
10.0°C
0.5°C
10.0°C
25 Hz
85 Hz
25 Hz
85 Hz
25 Hz
85 Hz
0000
9999
User
value
ENGLISH
- 25 -

Publicité

Chapitres

Table des Matières
loading

Produits Connexes pour Tecumseh INFINEE

Table des Matières