Inv Softstart Fail
Alarm Code:34
Charger Fail
Alarm Code:15
Battery Over Voltage
Alarm Code:16
Fatal eeprom Fault
Alarm Code:A3
Negative power Fault
Alarm Code: E1
Parallel cable loss
Alarm Code: E2
Parallel system battery
status
Alarm Code: E6
Line input different
Alarm Code: E7
Bypass input different
Alarm Code: E8
Power strategy different
Alarm Code: E9
Rate power different
Alarm Code: EA
HE in parallel
Alarm Code: EB
Redundancy lost
Alarm Code:ED
Indique que l'étage inverter ne peut
pas démarrer de facon correcte
Défaut chargeur
Surtension batteries
Indique que l'onduleur a un problème
d'eeprom
In parallel system,power of UPS is
negative
In parallel system,parallel cable
disconnect
UPS1 connect battery,UPS2 without
battery
Parallel system,UPS1 line ok,UPS2
line loss
Parallel system,UPS1 bypass
ok,UPS2 Bypass loss
Parallel system,UPS OP
mode(normal ,converter,HE)
different
Parallel system rate power different
Parallel system,OP mode set as HE
Parallel system,Redundancy lost
alarm enable,system load is increase
Contacter dequatec
Surtension étage onduleur
L'onduleur arrete le chargeur jusqu'a ce que la
tension batteries soit appropriée.
Contacter Dequatec
Redundancy mode,the fault UPS turn to fault
mode without output
Increase mode,UPS1& UPS2 turn to fault mode
Disconnect parallel cable one turn to fault mode
Check battery connect status
Check the line input
Bypass different,not allow turn on UPS. Check
bypass input
Check UPS OP mode, Keep OP mode be the same
Rate power different,not allow turn on UPS. Keep
rate power be the same
HE not allow in parallel system,change OP mode
"Redundancy lost" only notice client that system
isn't redundancy。Redundancy lost alarm disable
can make this alarm disappear。