According to
the low voltage
directive:
2006/95/EC /
the EMC directive:
2004/108/EC
CC CC OC OC
CC CC OC OC
Ribbon connector
A
B
C
D
E
net weight
170
250 136 155 193
3,29 kg
170
250 136 155 193
3,79 kg
170
250 136 155 193
5,79 kg
170
250 136 155 193
6,49 kg
200
305 140 183 235
9,11 kg
300
425 175 255 355
15,36 kg
300
425 225 255 355
17,95 kg
MOUNTING INSTRUC TIONS
EN
Speed controller for single phase voltage controllable motors
Technical data
Voltage: 230 Vac - 50/60 Hz
Imax
ST2R1-15L25
1.5 A
ST2R1-25L25
2.5 A
ST2R1-35L25
3.5 A
ST2R1-50L25
5.0 A
ST2R1-75L25
7.5 A
Enclosure: RABS, V0-UL94, grey
Imax
ST2R1100L25
10.0 A
ST2R1130L25
13.0 A
The ST2R1 transformer speed controllers are based on the prin-
ciple of voltage control with auto-transformers. They are appli-
cable to voltage-controllable motors (230 V, 50/60 Hz) to control
the rotational speed (of fans, pumps, etc.).
With the built-in clock these transformer controllers can work
completely autonomously. When commissioning, two speeds
(High and Low) can be selected out of 80-100-120-150-170-190-
230 V. These High and Low speed operation time ranges can be
set in the clock together with a range of motor stops (day/week
program). This permits a perfect day/night control.
Mounting
The controllers are to be mounted vertically on a smooth sur-
face. Connect voltage supply, motor(s) and earth as shown in
the scheme with cables of the proper diameter and in accord-
ance with local regulations. On the mains side, a safety switch
with recommended pre-fuses has to be installed.
Wiring Diagram
L
main supply 230 Vac – 50/60 Hz
L1 unregulated output 230 Vac
N
neutral
U
regulated output to motor
Al
output to alarm
TK thermal contact
CC room thermostat (contact normally closed)
OC frost protection (contact normally open)
Pe earth
Operation modes
The ST2R controller has four basic modes. Each mode is displa-
yed on the LCD.
• STAND-BY: motor is not working (due to clock setting)
• STOPPED: motor is not working (controller is stopped by
pressing I/O button or TK alarm condition occurred)
• AUTO: motor speed depends on clock setting (High mode/
Low mode/Standby)
• HAND SETTING: controller enters High mode by pressing
UP button and Low mode by pressing DOWN button.
There are two ways of changing the mode:
• due to clock setting
gross weight
• via the buttons on the front panel (if user or installer
3,51 kg
password is set, the buttons are disabled until the correct
password is typed when prompted)
4,01 kg
6,00 kg
Passwords
6,70 kg
User code: used to protect from mode changing in Hand set-
ting mode.
9,40 kg
Installer code: used to protect from changing of the controller's
15,95 kg
state via the buttons (Auto/Stopped/Hand setting) and Menu
18,54 kg
entrance.
Default value is '0000' , which means unlocked keypad. When
rect code to allow changing the state or entering the menu.
After a password has been entered correctly, no password will
be asked for 60 min.
The ST2R changes its mode according to the real time clock at
Fuse
(5*20mm)
F-2.5 A-T
F-4.0 A-T
F-5.0 A-T
From / To
AUTO
F-8.0 A-T
F-12.5 A-T
AUTO
HAND
A/M or High/Low
Fuse
SETTING
change (RTC)
(6*32mm)
F-16.0 A-T
STOP
I/O
F-20.0 A-T
STAND-BY
automatically (RTC)
Modes changing (keypad is free)
From / To
AUTO
AUTO
(A/M & code) or
HAND
High/Low change
SETTING
(RTC)
STOP
(I/O & code)
STAND-BY
automatically (RTC)
Modes changing (keypad is locked)
When powered, the controller enters AUTO mode. In this mode
the user can enter HAND SETTING mode by pushing A/M but-
ton short or can enter Install menu by pushing the A/M button
for 3 seconds.
In HAND SETTING mode you can switch the controller in High
or Low Mode by pressing the UP or DOWN buttons. UP corre-
sponds to High Mode and DOWN corresponds to Low Mode. By
a single press of the A/M button the controller returns in AUTO
mode or when holding the A/M button for 3 seconds the user
can access the Installer menu.
The condition of the controller in AUTO mode depends on the
real time clock settings. By default these settings are:
High Set point
Low Set point
Standby (automati-
cally calculated)
User has the ability to change these predetermined values ei-
ther by changing them for the whole weekdays/weekends or
for a particular day (Monday, Tuesday, Wednesday ...). Also there
times from the mentioned above.
Alarm conditions
TK protection - alarm condition, declared with blinking message
on the LCD display "Motor High Temp, Check Motor" and Al out-
put is activated (230 Vac). When the problem is eliminated, the
user must press any button (except the AM button) for at least 5
seconds. Messages on the LCD lead the user through the steps
required for controller restart after TK detection. After accom-
plishing the last step, the controller enters STOPPED mode and
Al output is deactivated.
Other conditions
1. CC – room thermostat. At these terminals, external devices
can be connected which can stop and start the motor. Breaking
the control circuit stops the motor ("Standby CC" message is
-
HAND SETTING
STOP
STAND-BY
automatically
A/M
I/O
(RTC)
I/O
RTC
-
I/O
A/M
I/O
HAND SETTING
STOP
STAND-BY
(I/O &
automatically
(A/M & code)
code)
(RTC)
(I/O &
RTC
code)
-
(I/O & code)
(I/O &
(A/M & code)
code)
Monday – Friday
Saturday - Sunday
00:00-24:00
00:00-24:00
--:--
--:--
--:--
--:--

Publicité

loading

Sommaire des Matières pour CAIROX ST2R1-15L25

  • Page 1 ST2R1-15L25 - ST2R1-75L25 Default value is ‘0000’ , which means unlocked keypad. When MOUNTING INSTRUC TIONS According to Speed controller for single phase voltage controllable motors rect code to allow changing the state or entering the menu. the low voltage...
  • Page 2 Netspanning: 230 Vac - 50/60 Hz • Read parameters from USB device (ST2R) Artikelcode Bereik Zekering • Save parameters into USB device (ST2R) (5*20mm) ST2R1-15L25 1,5 A F-2,5 A-T • Export hex file (save parameters to external file in ‘IntelHEX ST2R1-25L25 2,5 A F-4,0 A-T format’...
  • Page 3 Menu structure drukken. Door een enkele druk op de A/M-toets keert de rege- thermostaat (contact normaal gesloten) laar terug naar AUTO-mode of het installatiemenu door de toets vorstbescherming (contact normaal geopend) gedurende 3 seconden in te drukken. On/Off or ESC/back alarmuitgang (230 Vac/1 A) aardingsaansluitingen De toestand van de regelaar in de AUTO-modus is afhankelijk...
  • Page 4 Intensité Fusible (5*20mm) De/à AUTO STOP STAND-BY ché sur l’écran LCD) et le variateur est en mode veille. Lorsque ST2R1-15L25 1,5 A F-2,5 A-T SETTING le circuit est ouvert à nouveau, le variateur retourne au dernier automatique- ST2R1-25L25 2,5 A...

Ce manuel est également adapté pour:

St2r1-25l25St2r1-35l25St2r1-50l25St2r1-75l25St2r1100l25St2r1130l25