INSTALLATION CHECKLIST
Verify sufficient HTL lubricant is on conduit plugs
(recommend approximately 1/8" bead around the first
thread of plug) and that all unused conduit entries on the
housing are closed with lubricated plugs. Verify conduit
plugs are installed to at least five (5) full threads into the
housing conduit entries.
REPLACEMENT PARTS
Crouse-Hinds Champ LED luminaires are designed to provide years of reliable lighting
performance. However, should the need for replacement parts arise, they are available
through your authorized Crouse-Hinds distributor.
Assistance may also be obtained through your local Eaton's Crouse-Hinds Division
representative or Sales Service Department, 1201 Wolf Street, Syracuse, New York
13208, Phone (866) 764-5454.
INSTALLATION - YOKE MOUNTING (Wall, Ceiling, Ground)
1.
For luminaires fitted with yoke mount, install using 1/2" bolts or lag screws. See
Figure B for yoke mounting details.
Note: Prior to making any adjustments to yoke, consider that the 5/16"-18 screws
shown in Figure C are threaded into the yoke bracket.
2.
To set yoke mount to the desired angle, loosen the (4) 5/16"-18 nuts shown in
Figure C.
3.
Ensure the (4) 5/16"-18 screws are torqued to 132 in-lbs (14.9 N-m).
4.
Set the yoke bracket to the desired angle, and tighten nuts to set bracket in
place.
5.
Torque the (4) 5/16"-18 nuts to 132 in-lbs (14.9 N-m).
!
WARNING - EXPLOSION HAZARD
When installed, the Luminaire may not be mounted outside the allowable range
shown in Figure A. Luminaire may only be mounted such that after install it is
oriented -90° to +45° from the 0° nominal shown in Figure A.
For Class II, Div. 1 and Simultaneous Presence Class I, Div. 2 and Class II
applications, the allowable mounting range is 0° to 45° only shown in Figure A.
IF 1892 • 04/20
GROUND
Figure A
Copyright
GENERAL MAINTENANCE
1.
Perform visual, electrical and mechanical inspections on a regular basis. The
environment and frequency of use should determine this. However, it is
recommended that checks be made at least once a year. We recommend an
Electrical Preventive Maintenance Program as described in the National Fire
Protection Association Bulletin NFPA 70B: Recommended Practice for Electrical
Equipment Maintenance (www.nfpa.org).
2.
The windows should be cleaned periodically to ensure continued lighting
performance. To clean, wipe the windows with a clean, damp cloth. If this is not
sufficient, use a mild soap or a liquid cleaner such as Collinite NCF or Duco #7.
Do not use an abrasive, strong alkaline or acid cleaner. It may result in damage.
3.
Visually check for undue heating evidenced by discoloration of wires or other
components, damaged parts or leakage evidenced by water or corrosion in the
interior. Contact Crouse-Hinds for instructions on replacement parts.
4.
Electrically check to make sure that all connections are clean and tight.
5.
Mechanically check that all parts are properly assembled.
6.
Bezel/LED compartment is a non-serviceable joint, do not loosen or open screws.
Mounting method
Wall (standard)
Yoke
Hub (DP1053MTK)
Note: Class II, Div.1 and Simultaneous Presence Class I, Div. 2 and Class II will be
limited to 0° to +45° aiming range only.
2020, Eaton's Crouse-Hinds Division
©
Figure B
Figure C
Angle range
Mounting surface
Fixed
Wall
+45° to -90°
Wall, Ceiling, Horizontal Surface/Ground
+45° to -90°
Wall, Ceiling, Horizontal Surface/Ground
Page 4