Motor Wires – See Table 2
NOTE: A MINIMUM OF 75ºC COPPER WIRE IS
MANDATORY.
Refer to the Table 2 for wire sizing and maximum wire
lengths. Charts are designed to limit voltage drop to 5%.
Figure 2 shows the terminal block where the motor and
input wires connect. The circuit board near the terminal
block is labeled to show where to connect the motor wires.
For all motors, the green wire from the motor must be
attached to the terminal labeled GND.
For 3Ø motors with red, black and yellow wires, connect
the red wire to RED, black wire to BLK and yellow wire to
YEL.
Note: If there is more than 50 feet of wire from the
controller to the motor, consult factory for selection of an
output load filter (load reactor).
Input Power
SHOCK OR ELECTROCUTION
DANGER
HAZARD
Connect a ground wire from the service panel to the
terminal marked GND. Controller has high leakage to
ground. Controller ground terminal must be connected to
the service entrance ground terminal. Failure to do so will
result in high voltage being present on the controller chassis.
Connect two "hot" wires from the 2 pole circuit breaker to
the terminals marked L1 and L2.
Table 2
Circuit
Model
Breaker
3AB2
30
5AB2
50
* Consult factory for selection of an output load filter (load reactor) for output wire lengths greater than 50 feet.
The input power system used must be a grounded power
system. The voltage measured from L1 to L2 must be in the
range of 196Vac to 265Vac. The voltage measured from
L1 to GND must be equal to the voltage measured from
L2 to GND. These voltages must be within the range of
120Vac +/- 10%. Reduced input voltage will reduce system
performance.
Do not use a Ground Fault Circuit Interrupter (GFCI) with
this product or nuisance tripping will result.
Wire and Conduit
Factory installed input and output power leads may be
supplied with the controller. Use 75º C or higher rated
UL type copper wire. Use of Metal Conduit with Metal
Conduit liquid tight Connectors is recommended for all
electrical connections.
Circuit Breaker, Wire and Generator Sizing
1Ø Input Wiring
Size
Length (ft)
10 AWG
179
8 AWG
261
6 AWG
244
4 AWG
390
L1
L2 GND
Incoming Power
Figure 2: Wiring Connections
3Ø Output Wiring*
Size
Length (ft)
14 AWG
50
12 AWG
50
GND RED BLK YEL
Wires to Motor
Generator
Size
(KW)
8100
13300
5